Open The Gas Shut-Off Valve; Checking The Static And The Supply Pressure - Viessmann VITOCROSSAL 200 Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Checking the static and the supply pressure

Static pressure
87 kW
12
115 to 311 kW
A
1. Close the gas shut-off valve.
2. Undo the screw inside test connector
A, but do not remove.
3. Connect the pressure tester at test
connector A.

4. Open the gas shut-off valve.

5. Check the static pressure (max.
60 mbar).
6. Record the actual value in the report
(on page 61).
(cont.)