Further details regarding the individual steps

Checking the high limit safety cut-out setting
The high limit safety cut-out must not be
set higher than 110 °C; if required, set it
to a maximum of 110 °C.
Filling the heating system with water and venting the system
Record the fill volume, water hardness
and pH value on page 30 and 31.
Filling siphon with water
Starting the heating system
Control unit operating and serv-
ice instructions, and neutralising
system operating instructions
Commissioning, inspection, maintenance
Control unit installation and serv-
ice instructions
Note
Observe the "Water quality require-
ments" on page 62.
1. Release the siphon and fill with water
(otherwise flue gas may escape).
2. Check that the condensate can drain
freely.
3. Refit the siphon.
1. Check the heating system pressure.
Permissible boiler operating pres-
sure: 4 bar
7