Further details regarding the individual steps
Total hardness
Feedwater
Boiler water Boiler
The pH value should be between 8.2 and 9.5.
Checking the diaphragm expansion vessel and system pressure
Note
Observe the diaphragm expansion ves-
sel manufacturer's instructions.
Carry out this test on a cold system.
1. Drain the system until the pressure
gauge indicates "0" or close the cap
valve on the diaphragm expansion
vessel and reduce the pressure in the
diaphragm expansion vessel.
2. If the pre-charge pressure of the dia-
phragm expansion vessel is lower
than the static system pressure, top
up with nitrogen until the pre-charge
pressure is raised by 0.1 to 0.2 bar.
Commissioning, inspection, maintenance
pH value
Water treatment
Medium
water
3. Top up your heating system with
water and vent until the filling pres-
sure of a cooled system is 0.1 to 0.2
bar higher than the pre-charge pres-
sure of the diaphragm expansion
vessel.
Permiss. operating pressure: 4 bar
(cont.)
Date
Metering
volume
31