Viessmann VITOCROSSAL 200 Instructions Manual page 18

Gas condensing boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
18
(cont.)
3. If the CO
content must be adjusted:
2
■ Remove cover B.
■ Turn adjusting screw A in small
increments (Torx 40) until the CO
content reaches the specified
range:
– Turning clockwise
→ CO
content rises
2
– Turning anti-clockwise
→ CO
content falls
2
4. Record the actual value in the report
(on page 61).
Rechecking the values
Regulate to the upper and lower out-
put using the burner control unit. If the
values do not match the permissible
CO
content according to the table on
2
page 16, repeat the steps for the
upper and lower output.
5. Press "S" E and "-" D simultane-
ously. The burner is now in operating
mode.
2