Gas Shut-Off Valve Connection; Gas Connection And Piping - Viessmann B2TB004 Installation Instructions Manual

Table of Contents

Advertisement

Boiler Connections
Connections
(continued)
Legend
A Gas connection 7
B Accessible manual gas shutoff valve
C Ground joint union
D Drip leg

Gas connection and piping

1. Refer to current CAN/CSA B149.1 and .2 or National
Fuel Gas Code ANSI Z223.1/NFPA 54, as well as
local codes for gas piping requirements and sizing.
Pipe size to the boiler must be determined based on:
- pipe length
- number of fittings
- type of gas
- maximum input requirements of all gas appliances
in the residence.
IMPORTANT
Design piping layout in such a way that piping does not
interfere with serviceable components.
IMPORTANT
The Vitodens 222-F B2TB has a factory pre-installed
flexible gas line for left, right or vertical installation.
14
¾
in. (NPT)
Vitodens 222-F, B2TB 19, 35, 68, 125 Installation
2. Before connecting boiler to gas line, install ground
joint union, capped drip leg and a manual equipment
shutoff valve as shown. Valves must be listed by a
nationally recognized testing agency. Make boiler gas
connection as shown (choose one of three locations).
3. Perform gas piping pressure test as described in the
following subsection.
IMPORTANT
Max. gas supply pressure: 14 "w.c.
4. Identify shutoff valves as such with a tab and
familiarize operator / ultimate owner of boiler with
these valves.
See Vitodens 222-F B2TB Service Instructions
for applicable system coding information.
WARNING
The gas supply piping must be leak tested before placing
the boiler in operation.
CAUTION
Ensure that gas piping is large enough for all appliances in
the residence. No noticeable gas pressure drop in the gas
line must occur when any unit (or combination of units)
lights or runs.

Gas shut-off valve connection

1. Make gas connections in accordance with codes
CAN/CSA B149.1 and .2 or National Fuel Gas Code
ANSI Z223.1/NFPA 54, as well as local codes.
2. Connect gas shutoff valve to the boiler gas
connection.
3. Once connected close gas shutoff valve on boiler.
Manual gas shutoff
Open
Closed