F1 Setting Of Out1 - SMC Networks ZSE30AF-#-#-X576 Operation Manual

Digital pressure switch
Table of Contents

Advertisement

■[F 1] Setting of OUT1
Set output method of OUT1.
The output turns on when the pressure exceeds the set value. The default setting of the output set value is
the central value between the atmospheric pressure and the upper limit of the rated pressure range.
The display colour depends on the condition of OUT1.
The default setting of the display colour is as follows: green display when the output is ON and red display
when the output is OFF.
For the operation of each setting, refer to "List of output modes" on page 27.
<Operation>
Press the
or
Select output mode
or
Press the
Select reversed output
or
Press the
output.
Pressure Setting
Set the pressure based on the setting procedure on page 20.
"P" becomes "n" when reversed output is selected. ([P_1]  [n_1])
Hysteresis mode: [P_1]
Window comparator mode: [P1L] [P1H]
button in function selection mode to display [F 1].
Press the
button.
button to select output mode.
Press the
button to set.
button to select reversed
Press the
button to set.
Press the
button to set.
Move on to setting of output mode.
Move on to setting of reversed output.
Move on to setting of pressure.
Move on to setting of hysteresis.
-25-
No.PS※※-OMV1001