System Configuration - Omron SYSMAC C200H Operation Manual

Temperature sensor unit
Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

System Configuration

DIP Switch Setting
C200H-TS101/102
1-2
System Configuration
4
These two
numbers
must
match
Cold-junc-
tion com-
pensating
resistor
All switches are set to OFF before shipment from the factory.
OFF: 0
ON
1
2
3 4
ON: 1
Number of Input Points
1
2
No. of Input Points
0 0 4 input points (Inputs
1 through 4)
0 1
1 input point (Input 1)
1 0
2 input points (Inputs
1 and 2)
1 1
Not Used
The Special I/O Units are not allocated the word number of the slot they are
mounted to. They are allocated word numbers according to the unit number
setting on the front panel (refer to page 2).
If possible, avoid mounting the Temperature Sensor Units in either of the two
rightmost CPU Rack slots. However, if this is unavoidable, use one of the
Programming Console Base Units (C200H-BP001 or C200H-BP002) when
mounting peripheral devices to the PC.
No Special I/O Units can be mounted on a C200H Slave Rack connected to a
Master on a PC other than a C200H.
The thermocouple or RTD registers the temperature and sends the data
through the Temperature Sensor Unit to the PC in 4-digit BCD. After the PC
processes this data, the data can be output to a display, or used for control-
ling system devices.
Terminal
block
Temperature Selector
3
Function
0
J Pt (0° through 100°C)/Pt (0°
through 100°C). Once this pin is set
to ON, this setting becomes invalid
and the temperature must be set
through the PC program.
1 Set the temperature depending on
PC program.
Section 1-2
Not Used