Bit Allocation - Omron SYSMAC C200H Operation Manual

Temperature sensor unit
Hide thumbs Also See for SYSMAC C200H:
Table of Contents

Advertisement

Bit Allocation

3-2
Bit Allocation
Direction
Word
no.
15
Output
n
Tempera-
ture speci-
fication
enable
Input
n + 1
Code
0: positive
1: negative
n + 2
Code
0: positive
1: negative
n + 3
Code
0: positive
1: negative
n + 4
Code
0: positive
1: negative
n + 5
Running
IR Bit Allocation
IR
Word
Bit
Output
n
00
01
through
07
08
through
13
14
15
14
13
12
11
Temperature specification
code no.: 00 through 25
1
0
x 10
x 10
Conversion data of Input 1
3
2
x 10
x 10
Conversion data of Input 2
3
2
x 10
x 10
Conversion data of Input 3
3
2
x 10
x 10
Conversion data of Input 4
3
2
x 10
x 10
Temperature specification
code no.: 00 through 25
1
0
x 10
x 10
Note n = 100 + 10 x unit no.
The four words from words n+6 through n+9 can be used as work bits. Refer
to the C200H Operation Manual for details.
Name
Data hold
When this bit is turned ON, conversion of the temperature input
data is stopped and data is returned to its status just prior to turning the
bit ON. When this bit is turned OFF, the temperature input data is
converted to BCD data in cycles.
---
Always turned OFF.
Temperature
These bits specify the temperature specification code number of the
specification
temperature sensing element used in the Unit. A total of 41 code
code number
numbers (thermocouple K (CA) = 11, thermocouple J (IC) = 4, L(Fe-CuNi)
= 4, platinum RTD JPt = 11, platinum RTD Pt= 11 numbers) can be
specified in 2-digit BCD from 00 through 25. (Refer to pages 3 and 16 for
details.) The temperature specification code number becomes valid after
the temperature specification setting flag (word n bit 15) is turned ON.
---
Not used. Always turned OFF.
Temperature
When this bit is turned ON, the temperature specification code number
specification
specified for word n bits 08 through 13 becomes valid. Be sure to confirm
enable
beforehand that the temperature specification switch (pin 3) on the back
panel has been set to the ON position and that the setting standby flag
(word n+5 bit 06) has also been turned ON. Otherwise the code number
is invalid.
Bit
10
09
08
07
06
1
x 10
1
x 10
1
x 10
1
x 10
Stand
Data
by for
inval-
id
set-
ting
Function
Section 3-2
05
04
03
02
01
0
x 10
0
x 10
0
x 10
0
x 10
Disconnection
Memory
detected
error
Input
Input
Input
Input
4
3
2
1
00
Data
hold
Setting
error
13

Advertisement

Table of Contents
loading

Table of Contents