5 Connecting to power supply
Select connec-
tion cable for Ex
applications
Connection via angle
plug connector
12
Warning:
Within galvanic plants as well as vessels with cathodic corrosion
protection there are considerable potential differences. Considerably
equalisation currents can be caused via the cable scrren when the
screen is earthed on both ends. To avoid this, the cable screen must
only connected to ground potential on one side of the switching
cabinet in such applications. The cable screen must not be connected
to the internal ground terminal in the sensor and the outer ground
terminal on the housing not to the potential equalisation!
Information:
The metal parts of the instrument (antenna, transmitter, concentric
tube, etc.) are conductive connected with the inner and outer ground
terminal on the housing. This connection exists either directly metallic
or with instruments with external electronics via the screen of the
special connection cable. You can find specifications to the potential
connections within the instrument in chapter "Technical data".
Take note of the corresponding installation regulations for Ex
applications.

5.2 Connection procedure

Proceed as follows:
Loosen the screw on the rear of the plug connector
1
Remove the plug connector and seal from VEGABAR 14
2
Remove the plug insert out of the plug housing
3
Fig. 3: Loosen the plug insert
1
Cable gland
Plug insert
2
3
Plug housing
Remove approx. 5 cm of the cable mantle, strip approx. 1 cm
4
insulation from the individual wires
Lead the cable through the cable gland into the plug housing
5
Connect the wire ends to the screw terminals according to the
6
wiring plan
3
2
1
VEGABAR 14