Digital Output 5 - 6; Digital Output 7 - 12 - Watlow EZ-ZONE PM User Manual

Integrated controller models
Hide thumbs Also See for EZ-ZONE PM:
Table of Contents

Advertisement

Óç
Warning:
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices . Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life .
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1 .31
mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number .
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals .
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent ground
loops .
Note:
The control output common terminal
and the digital common terminal are
referenced to different voltages and
must remain isolated .
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only . Temperature Code T4A
ç
Warning:
Explosion Hazard – Substitution of
component may impair suitability for
CLASS I, DIVISION 2 .
ç
Warning:
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances .
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc .) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor .
®
Wat lo w EZ-ZO N E
PM In t e g r a te d Co n t r o ll e r

Digital Output 5 - 6

Digital Output
Slot C
• Update rate 10 Hz
98
• Output voltage 24V
99
• Current limit, Output 5, 24 mA
CF
maximum
CD
• Current limit, Output 6, 10 mA
CE
maximum driving single pole
DIN-A-MITE
common
B5
• Capable of driving a 3-pole
collector out
D6
DIN-A-MITE
collector out
D5
• Open-circuit voltage 22 to
32VÎ (dc)
PM _ _ [2,4] _ _-_ _ _ _ _ _ _

Digital Output 7 - 12

Slot E
• Internal supply provides a
Common
constant power output of
B7
750mW
Collector out
D7
• Maximum output sink
Collector out
D8
current per output is 1.5A
Collector out
(external class 2 or SELV
D9
supply required)
Collector out
D10
• Total sink current for all
Collector out
D11
outputs not to exceed 8A
Collector out
• Do not connect outputs in
D12
parallel
Supply
Z7
PM [4,6,8] _ _ _ _- [C,D] _ _
_ _ _ _
25
_
_
Open Collector Outputs
B7 common
D7
D8
D9
D10
D11
D12
Z7 supply
Internal Circuitry
Chapter 2 Instal l and W i re

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents