Digital Input/Output Menu - Watlow EZ-ZONE RMC User Manual

Control module
Table of Contents

Advertisement

Parameter Name
Display
Description
Process Value (1 to 4)
[`Su; C ]
[ Su.C]
Source Value C
View the value of Source
C.
Process Value (1 to 4)
[`Su; d ]
Source Value D
[ Su.d]
View the value of Source
D.
Process Value (1 to 4)
[`Su; E ]
Source Value E
[ Su.E]
View the value of Source
E.
Process Value (1 to 4)
[oFSt]
[oFSt]
Offset
Set an offset to be ap-
plied to this function's
output.
Process Value (1 to 4)
[``o; u ]
Output Value
[ o.u]
View the value of this
function block's output.
No Dis-
Process Value (1 to 4)
Error
play
View reported cause
for Process output mal-
function.
[`dio]
[oPEr]

Digital Input/Output Menu

Digital Output (7 to 12)
[`do; S ]
Output State
[ do.S]
View the state of this
output.
Digital Input (7 to 12)
[`di; S ]
Input State
[ di.S]
View this event input
state.
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
®
Wa t low EZ-ZO N E
R M C Mo d u le
RMC Module • Operations Page
Range
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
[`off] Off (62)
[``on] On (63)
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
[`off] Off (62)
[``on] On (63)
[`off] Off (62)
[``on] On (63)
CIP
Class
Modbus
Default
Relative
Instance
Address
Attribute
hex (dec)
- - - -
3434
0x7E (126)
[offset 70]
1 to 4
0x12 (18)
- - - -
3436
0x7E (126)
[offset 70]
1 to 4
0x13 (19)
- - - -
3438
0x7E (126)
[offset 70]
1 to 4
0x14 (20)
0
3444
0x7E (126)
[offset 70]
1 to 4
0x17 (23)
3442
0x7E (126)
[offset 70]
1 to 4
- - - -
0x16 (22)
- - - -
3452
0x7E
[offset 70]
(126)
1 to 4
0x1B (27)
- - - -
1032
0x6A (106)
[offset 30]
7 to C (12)
- - - -
1040
0x6A (106)
[offset 30]
7 to C (12)
0xB (11)
39
Profibus
Parameter
Index
ID
- - - -
26018
- - - -
26019
- - - -
26020
- - - -
26023
- - - -
26022
- - - -
26027
90
6007
7
- - - -
6011
Chapter 3 Operati ons Pa ge
Data
Type
& Read/
Write
float
R
float
R
float
R
float
RWES
float
R
uint
R
uint
R
uint
R
R: Read
W: Write
E: EEPROM
S: User Set