5-4. Self-diagnostic Error Codes

5-4. Self-diagnostic Error Codes
Error code
Name of error
(Hexadecimal)
E20
BPU error
(H14)
E21
RAM error
(H15)
E22
RAM error
(H16)
E26
User ROM
checksum
(H1A)
error
E27
Intelligent
module
(H1B)
installation
error
E28
System
register error
(H1C)
E29
System bus
time out error
(H1D)
E30
Interrupt
error
(H1E)
E31
Interrupt
error
(H1F)
E32
Interrupt
error
(H20)
E33
Multi-CPU
data unmatch
(H21)
error
(CPU2 only)
48
Program
Description
execution
Stops
Probably a hardware
abnormality.
Stops
Probably an abnormality in
the internal RAM.
Stops
Probably an abnormality in
the optional ROM.
Stops
Intelligent modules
installed exceed the
limitations [e.g., more than
3 standard link modules
(such as MEWNET-P/-W
C-NET or C.C.U.) are
installed on the FP3].
Stops
Probably an abnormality in
the system register.
Stops
Probably a hardware
abnormality.
Stops
Probably a hardware
abnormality.
Stops
Interrupt program was
executed even if no
interrupt trigger turned ON.
Probably a hardware
abnormality or an
abnormality caused by
noise.
Stops
Interrupt program was
executed even when no
interrupt trigger was turned
ON.
Probably a hardware
abnormality or an
abnormality caused by
noise.
Probably an INT program
corresponding to the
interrupt trigger is missing.
CPU2
Occurs when a FP3 or
stops
FP10S is used as CPU2
for a multi-CPU system.
Steps to take
Please contact your dealer.
Please contact your dealer.
Re-make user ROM and try
operating again.
Turn OFF FP-C/FP3/FP5/FP10S/
FP10 power and configure intelligent
modules referring to the hardware
manual or technical sheets for each
CPU.
Set the mode of FP-C/FP3/FP5/
FP10S/FP10 to PROG. and initialize
system registers.
Please contact your dealer.
Please contact your dealer.
Turn OFF FP-C/FP3/FP5/FP10S/
FP10 power and check the
surrounding noise level.
Turn OFF FP-C/FP3/FP5/FP10S/
FP10 power and check the
surrounding noise level.
Set the mode of FP-C/FP3/FP5/
FP10S/FP10 to PROG. and make
an INT program which corresponds
to the interrupt trigger.
Please contact your dealer.