Panasonic FP3 Technical Manual page 51

Programmable, thermocouple input unit
Hide thumbs Also See for FP3:
Table of Contents

Advertisement

From the previous page.
S If an abnormality is detected (K1 is monitored), check the following items:
- Check if sensor cable is properly connected to the unit. Refer to page 24, "3-3. Wiring."
- Check if a zero point correction sensor (AFP84201) is properly connected.
- Check if the dip switches for sensor and temperature range selection (SW1 through SW4)
on the rear side of the unit.
(1) Turn OFF the power for the FP3/FP10S system.
(2) Remove the unit from the backplane by loosening the unit mounting screw.
(3) Check the settings.
When K type sensor is used: Be sure to set the SW4 to OFF.
Temperature
range setting
for K type
sensor
When J type sensor is used: Be sure to set the SW4 to ON.
Temperature range
setting for J type
Go to next page.
I/O connector
Dip switches
0 °C to 200 °C/
32 °F to 392 °F
ON OFF
SW1
SW2
SW3
SW4
0 °C to 200 °C/
32 °F to 392 °F
sensor
ON OFF
SW1
SW2
SW3
SW4
0 °C to 400 °C/
0 °C to 600 °C/
32 °F to 752 °F
32 °F to 1112 °F
ON OFF
ON OFF
0 °C to 400 °C/
0 °C to 600 °C/
32 °F to 752 °F
32 °F to 1112 °F
ON OFF
ON OFF
5-2. Troubleshooting
0 °C to 1000 °C/
32 °F to 1832 °F
ON OFF
45