2.3.1 Details of troubleshooting procedure for PAM
1) PAM shutdown due to error
1) When the DC voltage detection circuit sends a signal exceeding the specified voltage to the microcomputer
DC voltage of 400 V or higher (detection circuit input voltage of about 4.6 V or higher) [IC1 69 pin]
– When an error is detected
PAM IGBT turns OFF.
Compressor turns OFF.
All units shut down completely when the error occurs four times.
2) When the outdoor unit clock waveform differs from the specified value immediately before the PAM IGBT turns ON
When there is no clock waveform input
When a clock signal of other than specified power source frequency (60Hz) is input
– When an error is detected
PAM IGBT does not turn ON.
Compressor operates normally.
Complete shutdown does not occur.
2) PAM error indication
In case of error "1)"
– An error signal is sent to the indoor unit as soon as an error is generated.
Malfunction No. 14-0 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is generated.
The LED continues flashing in the 14-time cycle even after the compressor stops operating.
The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.
In case of error "2)"
– An error signal is sent to the indoor unit as soon as an error is judged.
Malfunction No. 14-1 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is judged.
The LED on the outdoor unit flashes in normal pattern when the compressor stops operating.
(Compressor OFF or Thermostat OFF from remote control)
* When a user complains that the air conditioner does not provide sufficient cool air or warm air
In addition to conventional error-generating reasons, there is a possibility that the PAM IGBT does not turn ON even if the compressor is operating.
In that case, the DC voltage does not rise even though the compressor is operating, and lowers to the 180-VDC level.
– Check items
Clock circuit check
PAM IGBT check