Allen-Bradley MicroLogix 1200 User Manual page 75

Hide thumbs Also See for MicroLogix 1200:
Table of Contents

Advertisement

White with Orange Stripes
Shrink Tubing Recommended
Multiple Cable Connection
When connecting multiple cables to the DH-485 connector, use the
following diagram.
to Next Device
Table 4.4 Connections using Belden #3106A Cable
For this Wire/Pair
Shield/Drain
Blue
White/Orange
Table 4.5 Connections using Belden #9842 Cable
For this Wire/Pair
Shield/Drain
Blue/White
White/Orange
(1)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.
Orange with White Stripes
Blue (#3106A) or
Blue with White
Stripes (#9842)
Connect this Wire
Non-jacketed
Blue
White with Orange Stripe
Orange with White Stripe
Connect this Wire
Non-jacketed
White with Blue Stripe
Blue with White Stripe
White with Orange Stripe
Orange with White Stripe
Publication 1762-UM001D-EN-P - March 2004
Communication Connections
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
Drain Wire
to Previous Device
To this Terminal
Terminal 2 - Shield
Terminal 3 - (Common)
Terminal 4 - (Data B)
Terminal 5 - (Data A)
To this Terminal
Terminal 2 - Shield
Cut back - no connection
Terminal 3 - (Common)
Terminal 4 - (Data B)
Terminal 5 - (Data A)
4-11
(1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents