Table A.15 Relay Contact Ratings (1762-OW8 and 1762-OW16)
Maximum Volts
240V ac
120V ac
125V dc
24V dc
(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the applied dc voltage. For example, 28 VA/48V dc =
0.58A. For dc voltage applications less than 14V, the make/break ratings for relay contacts cannot exceed 2A.
(2) 1.5A above 40°C.
Publication 1762-UM001D-EN-P - March 2004
1762-OB8
Group 1: Outputs 0
to 7
Verified by one of the following dielectric
tests: 1200V ac for 1 sec. or 1697V dc for 1
sec.
75V dc working voltage (IEC Class 2
reinforced insulation)
Not Applicable
1
7
101
Amperes
Make
Break
7.5A
0.75A
15A
1.5A
(1)
0.22A
(2)
1.2A
1762-OB16
1762-OW8
Group 1: Outputs 0
Group 1:
to 15
Outputs 0 to 3
Group 2:
Outputs 4 to 7
Verified by one of the following dielectric tests:
1836V ac for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests:
The input rfi filter units are designed to be used with the following adjustable frequency ac drives:
1305;
1336 plus;
1336 plus ii;
1336 force;
1336 impact (18 pages)