Table of Contents System Directories ............................... 1 System General Purpose Directory ........................21 System Flow Control Directory..........................26 System Volume Accuracy Directory ........................28 System Temperature & Density Directory ......................32 System Pressure Directory ............................ 33 System Read Only Directory ..........................33 System Communication Directory ..........................
Program Program Code Function Code Description Entry Code System Directories System Configuration Directory Number of Products Enter: "1" One Product "2" Two Products "3" Three Products "4" Four Products Number of Additive Enter: "0" No Additive Injectors Injectors "1" One Additive Injector "2"...
Page 13
"08" Additive Relay 8 (ADD8) "09" Pulse Output (POT3) __ __ Note: This code is only available for use if the Quad OPV option has been purchased with the AccuLoad II. D/C Output Relay 4 Enter: "00" No Assignment (N/A) Terminals 17 &...
Page 20
Program Program Code Function Code Description Entry Code 4-20 Channel #1 Enter: Two digit number indicating Terminals 19 & 20 the use of this 4-20 Channel. First digit: "0" Channel Not Used "1" Product 1 "2" Product 2 "3" Product 3 "4"...
Page 21
Program Program Code Function Code Description Entry Code 4-20 Channel #4 Enter: Two digit number indicating Terminals 71 & 72 the use of this 4-20 Channel. First digit: "0" Channel Not Used "1" Product 1 "2" Product 2 "3" Product 3 "4"...
Page 22
Program Program Code Function Code Description Entry Code Additive Injector Enter: Four digit number indicating #2 Plumbing the products that this additive injector is plumbed into. 1st digit - Product #1 2nd digit - Product #2 3rd digit - Product #3 4th digit - Product #4 A zero in the digit indicates that the injector is not plumbed...
Page 23
Program Program Code Function Code Description Entry Code Additive Injector Enter: Four digit number indicating #4 Plumbing the products that this additive injector is plumbed into. 1st digit - Product #1 2nd digit - Product #2 3rd digit - Product #3 4th digit - Product #4 A zero in the digit indicates that the injector is not plumbed...
Page 24
Program Program Code Function Code Description Entry Code Additive Injector Enter: Four digit number indicating #6 Plumbing the products that this additive injector is plumbed into. 1st digit - Product #1 2nd digit - Product #2 3rd digit - Product #3 4th digit - Product #4 A zero in the digit indicates that the injector is not plumbed...
Page 25
Note: Entering the above number will program the AccuLoad II to a typical Input and Output configuration for the number of products selected. Refer to manual MN06066L for input and output assignments when using this method of configuring the AccuLoad II-RBU.
Program Program Code Function Code Description Entry Code System General Purpose Directory System Alarm Check/Reset Read only, Press E to clear None Available Alarms A2: Print Cover Open E4: Printer Error A4: Print Cover Open F1: Add 1 Feedback B2: Buffer Overflow F2: Add 2 Feedback B4: Buffer Overflow F3: Add 3 Feedback...
Page 27
Program Program Code Function Code Description Entry Code Product 2 Alarm Check/Reset Read only, Press E to clear None Available Alarms BH: Blend High LF: Low Flow BL: Blend Low LP: Low Pressure BP: Back Pressure LT: Low Temperature CF: Not Configured Flow OA: Overrun DA: Program Code PR: Pressure Transducer...
Page 28
Program Program Code Function Code Description Entry Code Product 4 Alarm Check/Reset Read only, Press E to clear None Available Alarms BH: Blend High LF: Low Flow BL: Blend Low LP: Low Pressure BP: Back Pressure LT: Low Temperature CF: Not Configured Flow OA: Overrun DA: Program Code PR: Pressure Transducer...
Page 29
Program Program Code Function Code Description Entry Code 112-139 Unassigned at Present 112-139 Protection of Program Enter: "0" for Weights and Measures Mode Codes 180-189 "1" for Program Mode Local Mode Alarm Enter: One digit from one to Clearing nine indicates the number of alarms that can be cleared during a transaction when in the Run Mode.
Page 30
"ENTER" key. The display can be changed using the character set resident in the AccuLoad II. (See Appendix for entry numbers and to record translation.) Note: This code applies to RBU-05 and above firmware.
Program Program Code Function Code Description Entry Code System Flow Control Directory Low Flow Start Volume Enter: Four digits in whole units (e.g., 0100) __ __ __ __ Note: The larger of the volumes as programmed in this code or calculated in code 202 will be used as the low flow start volume. Low Flow Start Enter: Two digits in whole percentage...
Page 32
"4" for Product 4 Note: If a recipe of 100% of the Clean Line Product is being loaded the AccuLoad II will not shut down and restart to add the Clean Line Product. This note applies to RBU-08 and above firmware.
Program Program Code Function Code Description Entry Code Clean Line Alarm Enter: Two digits in volume Limit of under delivery of the clean line volume allowed. (e.g., 10) __ __ Ratio Adjustment Enter: Three digits in tenths to Factor speed up response of blend values (e.g., 20.0) __ __ .
Page 34
Program Program Code Function Code Description Entry Code Auto Preset Increment Enter: Four digits in whole units to increment the auto preset. (e.g., 0100 units) "0000" disables option __ __ __ __ Blank Downcounter Enter: "0" Downcounter to be Displayed "1"...
Page 35
Program Program Code Function Code Description Entry Code Display Resolution Enter: "0" Whole Unit Display "1" Tenth Unit Display "2" Hundredth Unit Display "3" Tens Unit Display Proving Modes Enter: "0" Not Proving "1" Weights and Measures Proving "2" High-Speed Proving Proving Output Enter: "0"...
Page 36
Program Program Code Function Code Description Entry Code Combinated Pulse Enter: "0" Raw Pulse Output Output "1" Gross Pulse Output "2" Gross @ Standard Temperature Output "3" Net Output "4" Mass Output Note: This code applies to RBU-02 and above firmware. Combinated Pulse Enter: Six digits defining the...
Program Program Code Function Code Description Entry Code System Temperature & Density Directory 401-439 Unassigned at Present 401-439 Protection of Program Enter: "0" for Weights and Measures Mode Codes 480-489 "1" for Program Mode Temperature Units Enter: "0" No Temperature Used "1"...
Program Program Code Function Code Description Entry Code System Pressure Directory 501-539 Unassigned at Present 501-539 Protection of Program Enter: "0" for Weights and Measures Mode Codes 580-589 "1" for Program Mode Pressure Units Enter: "0" No Pressure Used "1" Psi "2"...
"0" for Poll Only Communication "1" for Poll and Authorize Control "2" for Remote Control "3" for Auto Out Printer (one AccuLoad II per printer) "4" for Shared Auto Out Printer (up to 16 AccuLoad IIs per printer) Issue/Rev. 03 (8/97)
Page 40
Program Program Code Function Code Description Entry Code EIA-232 Baud Rate Enter: "0" for 110 Baud "1" for 150 Baud "2" for 300 Baud "3" for 600 Baud "4" for 1200 Baud "5" for 2400 Baud "6" for 3600 Baud "7"...
Page 41
Program Program Code Function Code Description Entry Code EIA-485 Data Format Enter: "0" EIA-485 7 Bits Even "1" EIA-485 7 Bits Odd "2" EIA-485 7 Bits None "3" EIA-485 8 Bits Even "4" EIA-485 8 Bits Odd "5" EIA-485 8 Bits None Communication Enter: Two digit number to...
Page 42
Program Program Code Function Code Description Entry Code Prompt Message #2 Enter: Up to 20 characters for prompt message (e.g., Enter Company ID) _______________ Prompt Message #3 Enter: Up to 20 characters for prompt message (e.g., Enter Trailer No) _______________ Prompt Message #4 Enter: Up to 20 characters...
Page 43
Program Program Code Function Code Description Entry Code 725-739 Unassigned at Present 725-739 Protection of Program Enter: "0" for Weights and Measures Mode Codes 780-789 "1" for Program Mode Communication Link Enter: "0" for No Program Code Values Programming "1" for Program Values Only "2"...
Page 44
Out Alarm "1" for Local SP Alarm "2" for Program SP Alarm Shared Printer Out Enter: Two digits in minutes Timer of time that the AccuLoad II will wait before Alarming. __ __ EIA-232 Printer Enter: "0" No 232 Security Security "1"...
Page 45
Program Program Code Function Code Description Entry Code EIA-485 Printer Enter: "0" No 485 Security Security "1" XON/XOFF "2" DEC Protocol "3" PTB - FX Protocol "4" PTB - LQ Protocol Note: Options 3 and 4 of this code apply to RBU-02 and above firmware. Shared Printer Enter: "0"...
Page 46
Program Program Code Function Code Description Entry Code Select Load Enter: Three digit number indicating Parameters to Print the load averages that will be printed on the Product Receipt Ticket. 1st digit - Load Average Temperature 2nd digit - Load Average Density 3rd digit - Reference Density A zero in the digit indicates the load average will not be printed,...
Page 47
Program Program Code Function Code Description Entry Code Define Delivery Enter: Ten digits in the form of Report four digits for the current line (0000), three digits for the column number that the data will start at (000), and the item that will be printed (000) on the delivery report.
Program Program Code Function Code Description Entry Code System Input/Output Directory Additive Injector Stop Enter: "0" Additive stop at end of batch (Option 1) "1" Additive stop at programmed stop volume with no recalculation of Additive. (Option 2) "2" Additive stop at programmed stop volume with recalculation of additive (Option 3) Additive Injector...
Page 49
Program Program Code Function Code Description Entry Code Permissive #1 Enter: "0" No Permissive 1 "1" Permissive 1 Transaction start only "2" Permissive 1 Continuously "3" Start Permissive 1 "4" Batch Permissive 1 "5" Remote Start Note: Option 5 requires hardware jumpers (see installation manual). Permissive #1 Enter: Up to 20 characters...
Page 50
Program Program Code Function Code Description Entry Code Additive #2 Message Enter: Up to nine characters for Additive #2 Message on the Product Receipt Ticket. (e.g., Dye) _______________ Additive #3 Message Enter: Up to nine characters for Additive #3 Message on the Product Receipt Ticket.
Page 51
Program Program Code Function Code Description Entry Code Additive Injector #1 Enter: "0" No Injector 1 Feedback Feedback "1" Injector 1 Feedback/Control "2" Injector 1 Feedback Only Additive Injector #1 Enter: Six digits defining Volume per Cycle the volume of product to be injected for each Additive Injector cycle (e.g., 001.000) __ __ __ .
Page 52
Program Program Code Function Code Description Entry Code Additive Injector #5 Enter: Six digits defining Volume per Cycle the volume of product to be injected for each Additive Injector cycle (e.g., 001.000) __ __ __ . __ __ __ Additive Injector #6 Enter: "0"...
Page 53
(e.g., 7.812500E-03 conversion for ounce to gallon.) Note: If set to zero the AccuLoad II will not add the Additive volumes to the delivered product volumes. __ . __ __ __ __ __ __ E __ __ __...
Page 54
Program Program Code Function Code Description Entry Code Injector #6 Feedback Enter: Three digits in seconds Delay allowed between feedbacks before an alarm. __ __ __ Injector #7 Feedback Enter: Three digits in seconds Delay allowed between feedbacks before an alarm. __ __ __ Injector #8 Feedback Enter:...
Program Program Code Function Code Description Entry Code Maximum Units Enter: Five digits in tenth 4-20 Channel #3 units for maximum units at 20 mA. (e.g., 450.0) __ __ __ __ . __ Note: If the channel is selected for temperature the first digit entered is the sign + or -. Where 0 = +, 1 = -. Minimum Units Enter: Five digits in tenth...
Page 56
Program Program Code Function Code Description Entry Code Diagnostic AccuLoad II Model Number Read Only Diagnostic ACM Model Number Read Only Diagnostic System Messages Read Only Diagnostic Calibration Event Counter None Note: This code applies to RBU-10 and above firmware.
Page 57
Program Program Code Function Code Description Entry Code Diagnostic Meter Pulse Channel 2 Contact None Diagnostic Meter Pulse Channel 3 Active None Diagnostic Meter Pulse Channel 3 Contact None Diagnostic Meter Pulse Channel 4 Active None Diagnostic Meter Pulse Channel 4 Contact None Diagnostic Contact Input Test...
Page 58
Program Program Code Function Code Description Entry Code Diagnostic Clear Configurable Report None Note: This code applies to RBU-04 and above firmware. 965-990 Unassigned at Present 965-990 Diagnostic Relay Test None Diagnostic Ram Test None Diagnostic Power-up Diagnostics None Diagnostic See Operator Reference Manual None Diagnostic...
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Product Directories Product General Purpose Directory 101-139 Unassigned at Present Protection of Program Enter: "0" for Weights and Measures Mode Codes 180 - 189 "1" for Program Mode Product Selection Enter: "0"...
Page 60
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Flow Tolerance Enter: One digit as a percentage of First High Flow Rate (e.g., 7) Zero Flow Timer Enter: Two digits in seconds (e.g., 15) "00" disables the alarm __ __ __ __ __ __...
(e.g., 0400) _____ _____ _____ ______ Note: If flow rate is set at zero the AccuLoad II will ignore codes 344 through 348. Meter Factor #2 Enter: Five digits as one whole number followed by four decimals (e.g., 1.0040) _._____ _._____ _._____ _._____...
Page 62
Meter Factor #4 per minute (e.g., 0080) _____ _____ _____ _____ Note: If flow rate is set at zero the AccuLoad II will ignore code 348. Meter Factor #4 Enter: Five digits as one whole number followed by four decimals (e.g., 1.0058) _._____ _._____ _._____ _._____...
Page 63
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Dual Pulse Error Enter: Three digits indicating Count the number of error counts from the dual pulse Comparator prior to alarming. (e.g., 050) ______ ______ ______ ______ Note: "000"...
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Transmitter Type Enter: "0" Single Channel "1" Dual Channel 394-399 Unassigned at Present Product Temperature & Density Directory 401-439 Unassigned at Present Protection of Program Enter: "0" for Weights and Measures Mode Codes 480-489 "1"...
Page 65
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 High Temperature Enter: Four digits. The Alarm first digit indicates polarity. First digit "0" = Positive First digit "1" = Negative The last three digits indicate temperature in whole degrees.
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Product Pressure Directory Minimum Back Enter: Four digits to select Pressure Flow the minimum flow rate allowed Rate Setting during back pressure operation in whole units per minute. (e.g., 0100) "0000"...
Page 67
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 507-539 Unassigned at Present Protection of Program Enter: "0" for Weights and Measures Mode codes 580-589 "1" for Program Mode Compressibility Factor Enter: Five digit compressibility factor used in calculating the CPL (e.g., 39600 entered represents 0.000039600)
Page 68
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Middle Product Vapor Enter: Four digits in Degrees Pressure (P2) C or Degrees F that corresponds Temperature to the middle vapor pressure in code 545. First digit "0" = Plus Degrees First digit "1"...
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Product Read Only Directory Raw Non-resettable To be read only None None None None Volume Gross Non-resettable To be read only None None None None Volume Gross at Standard To be read only None None...
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Product Communications Directory HM Classification Enter: First 20 characters of for Printout the classification. Prod1______________________________ Prod2______________________________ Prod3______________________________ Prod4______________________________ HM Classification Enter: Second 20 characters of for Printout the classification.
Program Code Function Code Description Prod 1 Prod 2 Prod 3 Prod 4 Product Inputs & Outputs Directory 801-839 Unassigned at Present Protection of Program Enter: "0" for Weights and Measures Mode Codes 880-889 "1" for Program Mode 841-899 Unassigned at Present Product Diagnostics Directory 901-939 Unassigned at Present...
Program Program Code Function Code Description Entry Code Blend Recipe Directories __00 Blend Recipe # __ Directory __00 __01 Blend Recipe Enter: "0" Recipe disabled __01 "1" Recipe enabled __02 Blend Recipe Name Enter: Up to nine characters for __02 recipe identifier.
Page 73
Program Program Code Function Code Description Entry Code __12 Product #3's high, To be read only __12 2nd high and low flow rates __13 Product #4's high, To be read only __13 2nd high and low flow rates __14-__39 Unassigned at Present __14-__39 __40 Protection of Program Enter:...
Page 74
Program Program Code Function Code Description Entry Code __46 Product #4 Enter: Four digits in tenth __46 Percentage of a percent (e.g., 050.0). __ __ __ __ Note: Codes __43, __44, __45, and __46 must add up to 100 %. __47 Product using Enter: Four digit number indicating...
Page 75
Program Program Code Function Code Description Entry Code __49 Product using Enter: Four digit number indicating __49 Injector #3 the products this injector is used with. 1st digit - Product 1 2nd digit - Product 2 3rd digit - Product 3 4th digit - Product 4 A zero in the digit indicates the injector will not be used...
Page 76
Program Program Code Function Code Description Entry Code __52 Product using Enter: Four digit number indicating __52 Injector #6 the products this injector is used with. 1st digit - Product 1 2nd digit - Product 2 3rd digit - Product 3 4th digit - Product 4 A zero in the digit indicates the injector will not be used...
Program Program Code Function Code Description Entry Code __55 Recipe Correction Enter: Five digits as one whole number __55 Factor followed by four decimals (e.g., 1.1000) __. __ __ __ __ __80 Clean Line Enter: "0" Not Used __80 Deduct "1"...
Page 78
Code Recipe 1 Recipe 2 Recipe 3 Recipe 4 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 80
Code Recipe 5 Recipe 6 Recipe 7 Recipe 8 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 82
Code Recipe 9 Recipe 10 Recipe 11 Recipe 12 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 84
Code Recipe 13 Recipe 14 Recipe 15 Recipe 16 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 86
Code Recipe 17 Recipe 18 Recipe 19 Recipe 20 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 88
Code Recipe 21 Recipe 22 Recipe 23 Recipe 24 __01 __02 _____________ ______________ _____________ _____________ __03 Read Only Read Only Read Only Read Only __04 Read Only Read Only Read Only Read Only __05 Read Only Read Only Read Only Read Only __06 Read Only...
Page 93
Output Entry Number Entry Description Translation Length Batch Trans Preset Completed 094,095,**096 Preset batch volume exceeds 3 * 24 the maximum permitted. 097,098,**099 Preset batch volume is below 3 * 24 the minimum required. 100,**101 The minimum preset for this 2 * 24 recipe is 102,103,...
Page 94
Appendix II The following table provides the entry number, description of the data entry, the code reference (if any), the number of columns required for the data, and the bytes that the item will require when saved in local storage. The following designations are used in the byte column of the table: The entry is programmable via a program code entry and is never saved in local storage.
Page 95
Entry Description Code Ref Columns Bytes First User Selected Volume for the Recipe Volume for the First Batch Run First User Selected Volume for the Recipe Volume for the Second Batch Run First User Selected Volume for the Recipe Volume for the Third Batch Run First User Selected Volume for the Recipe Volume for the Fourth Batch Run...
Page 96
Entry Description Code Ref Columns Bytes Recipe Name for the Second Recipe Run for the R__02 Transaction Recipe Name for the Third Recipe Run for the R__02 Recipe Name for the Fourth Recipe Run for the R__02 Transaction Recipe Name for the Fifth Recipe Run for the R__02 Transaction Recipe Name for the Sixth Recipe Run for the...
Page 97
Entry Description Code Ref Columns Bytes Transaction Volume of the Third Recipe Run, **** Third User Selected Volume Transaction Volume of the Fourth Recipe Run, **** Third User Selected Volume Transaction Volume of the Fifth Recipe Run, Third **** User Selected Volume Transaction Volume of the Sixth Recipe Run, **** Third User Selected Volume...
Page 98
Entry Description Code Ref Columns Bytes Additive Injector # 2 Volume for the Fourth Batch Additive Injector # 2 Volume for the Fifth Batch Additive Injector # 2 Volume for the Sixth Batch Additive Injector # 3 Volume for the First Batch Additive Injector # 3 Volume for the Second Batch Additive Injector # 3 Volume for the Third Batch Additive Injector # 3 Volume for the Fourth Batch...
Page 99
Entry Description Code Ref Columns Bytes Additive Injector # 5 Volume for the Fifth Batch Additive Injector # 5 Volume for the Sixth Batch Additive Injector # 6 Volume for the First Batch Additive Injector # 6 Volume for the Second Batch Additive Injector # 6 Volume for the Third Batch Additive Injector # 6 Volume for the Fourth Batch Additive Injector # 6 Volume for the Fifth Batch...
Page 101
Entry Description Code Ref Columns Bytes First User Selected Volume for Product Two, Sixth 4 ** Batch First User Selected Volume for Product Three, First Batch First User Selected Volume for Product Three, 4 ** Second Batch First User Selected Volume for Product Three, 4 ** Third Batch First User Selected Volume for Product Three,...
Page 102
Entry Description Code Ref Columns Bytes Second User Selected Volume for Product Two, First Batch Second User Selected Volume for Product Two, 4 ** Second Batch Second User Selected Volume for Product Two, 4 ** Third Batch Second User Selected Volume for Product Two, 4 ** Fourth Batch Second User Selected Volume for Product Two,...
Page 103
Entry Description Code Ref Columns Bytes Third User Selected Volume for Product One, 4 ** Second Batch Third User Selected Volume for Product One, 4 ** Third Batch Third User Selected Volume for Product One, 4 ** Fourth Batch Third User Selected Volume for Product One, Fifth 4 ** Batch Third User Selected Volume for Product One,...
Page 104
Entry Description Code Ref Columns Bytes Third User Selected Volume for Product Four, Third Batch Third User Selected Volume for Product Four, 4 ** Fourth Batch Third User Selected Volume for Product Four, 4 ** Fifth Batch Third User Selected Volume for Product Four, 4 ** Sixth Batch Transaction Volume of Product One, First User...
Page 105
Entry Description Code Ref Columns Bytes Load Average Temperature for the Fourth Batch Load Average Temperature for the Fifth Batch Load Average Temperature for the Sixth Batch Load Average Temperature for Product One, First Batch Load Average Temperature for Product One, Second Batch Load Average Temperature for Product One, Third Batch...
Page 106
Entry Description Code Ref Columns Bytes Load Average Temperature for Product Three, Fifth Batch Load Average Temperature for Product Three, Sixth Batch Load Average Temperature for Product Four, First Batch Load Average Temperature for Product Four, Second Batch Load Average Temperature for Product Four, Third Batch Load Average Temperature for Product Four, Fourth Batch...
Page 107
Entry Description Code Ref Columns Bytes Load Average Density, Third Batch Load Average Density, Fourth Batch Load Average Density, Fifth Batch Load Average Density, Sixth Batch Load Average Density, Product One, First Batch Load Average Density, Product One, Second Batch Load Average Density, Product One, Third Batch Load Average Density, Product One, Fourth Batch Load Average Density, Product One, Fifth Batch...
Page 108
Entry Description Code Ref Columns Bytes Load Average Density, Product Four, Sixth Batch Transaction Load Average Density, Product One Transaction Load Average Density, Product Two Transaction Load Average Density, Product Three Transaction Load Average Density, Product Four Reference Density Product One P442 Reference Density Product Two P442...
Page 109
Entry Description Code Ref Columns Bytes Volume Units S341 Mass Units S445 Additive Injector Units S857 Form Feed End of Form Form Feed Rev. 9 firmware and above. First User Selected Volume for Product One, Non-resettable Total Rev. 9 firmware and above. Second User Selected Volume for Product One, Non-resettable Total Rev.
Page 110
Entry Description Code Ref Columns Bytes Batch Completion Flag, Second Batch Rev. 11 firmware and above Batch Completion Flag, Third Batch Rev. 11 firmware and above Batch Completion Flag, Fourth Batch Rev. 11 firmware and above Batch Completion Flag, Fifth Batch Rev.
Page 112
0 = Clearable Entry Alarm 1 = Not Clearable PA: Power-fail (Set at entry 186) ZF: Zero Flow (Set at entry 212) HT: High Temperature LT: Low Temperature TP: Temperature Probe HP: High Pressure LP: Low Pressure PR: Pressure Transducer HD: High Density LD: Low Density DR: Density Transducer...