8.4.1.5 Temperature sensor malfunction diagnosis and solution.
Malfunction conditions
Potential causes
Trouble shooting:
Check the connections
between temperature
sensor and PCB. Are
the connections good?
Yes
Check the resistance value
of the sensor via Appendix 1
and Appendix 2
Is it normal?
No
Replace the sensor
If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED displays a failure.
Wiring mistake
Faulty sensor
Faulty PCB
No
Correct the connections.
Yes
Replace indoor or outdoor PCB.
51