Midea MCH2U-18PHH2 Service Manual page 48

Multi outdoor/ condensing units multi zone
Table of Contents

Advertisement

8.4.1.3 Zero-crossing signal detection error diagnosis and solution.
Malfunction conditions
Potential causes
Trouble shooting:
Check if the connections and
power supply is normal ?
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.
When PCB does not receive zero crossing signal feedback for
4 minutes or the zero crossing signal time interval is abnormal.
● Connection mistake
● Faulty PCB
Correct the connections . Turn on the
No
unit when the power supply is good .
48
PIC 4: Check point button, press 1 time for check
how many indoor units are connected.