Outdoor unit error display
MCH2U-18PHH2, MCH3U-27PHH2, MCH4U-36PHH2, MCH5U-48PHH2;
Display
E0
Outdoor unit EEPROM parameter error
E2
Communication malfunction between indoor and outdoor units
Communication malfunction between IPM board and outdoor main
E3
control board
Outdoor temperature sensor (coil sensor T3,ambient sensor T4,
E4
Compressor discharge sensor T5、indoor coil outlet pipe sensor T2B)
malfunction
Communication malfunction between indoor and
E1
outdoor units
E3
Indoor fan speed malfunction
E4
Indoor room temperature sensor (T1 ) malfunction
Evaporator coil temperature sensor (T2)
E5
malfunction
EE
Water-level alarm malfunction
F0
Current overload protection
Outdoor ambient temperature sensor (T4 )
F1
malfunction
Condenser coil temperature sensor (T3)
F2
malfunction
Compressor discharge temperature sensor (T5)
F3
malfunction
F4
Outdoor unit EEPROM parameter error
F5
Outdoor fan speed malfunction
Indoor coil outlet pipe sensor(Located on outdoor
F6
unit low pressure valve)
Communication malfunction between Cassette
F7
optional lift panel and the unit.
F8
Cassette optional lift panel malfunction
F9
Cassette optional lift panel not closed
P0
Inverter module (IPM) malfunction
P1
Over-voltage or under-voltage protection
P3
Low ambient temperature cut off in heating
P4
Compressor drive malfunction
——
Indoor units mode conflict
★ flash ,  light, X extinguished
LED STATUS
36
E2
——
——
——
——
E4
E4
E4
E0
E8
——
——
——
——
P6
E5
——
——
——
New indoor
Error
F4
E1
——
F2/F1/F3/F6