Midea MCH2U-18PHH2 Service Manual page 39

Multi outdoor/ condensing units multi zone
Table of Contents

Advertisement

11
Indoor unit D capacity demand code
12
Indoor unit E capacity demand code
13
Outdoor unit amendatory capacity demand
code
14
The frequency corresponding to the total
indoor units' amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor
control chip
17
Indoor unit A evaporator outlet temperature
(T
A)
2B
18
Indoor unit B evaporator outlet temperature
(T
B)
2B
19
Indoor unit C evaporator outlet temperature
(T
C)
2B
20
Indoor unit D evaporator outlet temperature
(T
D)
2B
21
Indoor unit E evaporator outlet temperature
(T
E)
2B
22
Indoor unit A room temperature (T
23
Indoor unit B room temperature (T
24
Indoor unit C room temperature (T
25
Indoor unit D room temperature (T
26
Indoor unit E room temperature (T
27
Indoor unit A evaporator temperature (T
28
Indoor unit B evaporator temperature (T
29
Indoor unit C evaporator temperature (T
30
Indoor unit D evaporator temperature (T
31
Indoor unit E evaporator temperature (T
32
Condenser pipe temperature (T3)
33
Outdoor ambient temperature (T4)
34
Compressor discharge temperature (TP)
35
AD value of current
36
AD value of voltage
37
EXV open angle for A indoor unit
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
If the temperature is lower than -9
9." If the temperature is higher than 70
shows "70." If the indoor unit is not connected, the digital display
shows: "――"
If the temperature is lower than 0 ℃, the digital display shows "0."
A)
1
If the temperature is higher than 50 ℃, the digital display shows
B)
1
"50." If the indoor unit is not connected, the digital display shows:
"――"
C)
1
D)
1
E)
1
A)
2
B)
2
C)
2
If the temperature is lower than -9 ℃, the digital display shows "-
9." If the temperature is higher than 70 ℃, the digital display
D)
2
shows "70." If the indoor unit is not connected, the digital display
E)
shows: "――"
2
The display value is between 30–129 ℃. If the temperature is
lower than 30 ℃, the digital display shows "30." If the temperature
is higher than 99 ℃, the digital display shows single and double
digits. For example, if the digital display shows "0.5", the
compressor discharge temperature is 105 ℃.
The display value is a hex number.
For example, the digital display tube shows "Cd", it means AD
value is 205.
Actual data/4.
If the value is higher than 99, the digital display shows single and
double digits.
For example, if the digital display shows "2.0", the EXV open
angle is 120×4=480p.
Frequency limit caused by IGBT
Bit7
radiator
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
39
, the digital display shows "-
, the digital display
The display
value is a
hexidecimal
number. For
example, the
digital display
show 2A, then

Hide quick links: