Interrupt Response Time; Overview - Siemens SIMATIC S7-300 Manual

Central processing unit
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

3. Multiply both values by the CPU-specific extension factor of the user program processing
4. Add the value of the interrupt-processing program sequences to the theoretical cycle
Response time
Table 7-6
Shortest response time
-
Now add I/O delay.
The result is the shortest response time.
7.5

Interrupt response time

7.5
7.5.1

Overview

Definition of the interrupt response time
The interrupt response time is the time that expires between the first occurrence of an
interrupt signal and the call of the first interrupt OB statement. Generally, the following is
valid: Interrupts having a higher priority take precedence. This means that the interrupt
response time is increased by the program processing time of the higher-priority interrupt
OBs and the interrupt OBs of equal priority which have not yet been executed (queued).
Process/diagnostic interrupt response times of the CPU
Table 7-7
CPU
CPU 315T-2 DP
* The integrated inputs/outputs for integrated technology do not have interrupt capability.
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
time (see table "CPU communication services").
time, multiplied by the number of triggering (or expected) interrupt events within the cycle
time.
The result you obtain is approximately the actual cycle time. Make a note of the result.
Calculating the response time
Process/diagnostic interrupt response times
Process interrupt response times
External
min.
0.4 ms
Longest response time
Multiply the actual cycle time by a factor of 2.
Then, calculate the delays in the inputs and
outputs and the DP cycle times on the
PROFIBUS DP network.
The result is the longest response time.
External
Integrated
max.
inputs/outputs
for integrated
technology*
0.7 ms
-
Cycle and response times
7.5 Interrupt response time
Diagnostic interrupt response
times
min.
Max.
0.4 ms
1.0 ms
7-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-300 cpu data: cpu 315-t-2 dp

Table of Contents