Table 5-1 Interrupt Blocks With Dpv1 Functionality - Siemens SIMATIC S7-300 Manual

Central processing unit
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Definition DPV1
The term DPV1 is defined as a functional extension of the acyclical services (to include new
interrupts, for example) provided by the DP protocol. Enhancement of the distributed I/O EN
50170 standard. All the changes concerning new DPV1 functions are included in IEC 61158/
EN 50170, volume 2, PROFIBUS.
Extended functions of DPV1
• Use of any DPV1 slaves from external vendors (in addition to the existing DPV0 and S7
• Selective handling of DPV1-specific interrupt events by new interrupt blocks.
• Reading/writing Sibs that conform to standards to the data record (although this can only
• User-friendly SFB for reading diagnostics.
Availability
The Technology CPU, serving as DP master at the MPI/DP interface, features the enhanced
DPV1 functionality.
Note
If you want to use the CPU as an intelligent DP slave, remember that it does not have DPV1
functionality.
Requirement for using the DPV1 functionality with DP slaves
For DPV1 slaves from other vendors, you will need a GSD file conforming to EN 50170,
revision 3 or later.
Interrupt blocks with DPV1 functionality
Table 5-1
OB
OB 40
OB 55
OB 56
OB 57
OB 82
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
slaves, of course).
be used for centralized modules).
Interrupt blocks with DPV1 functionality
Functionality
Process interrupt
DPV1: Status interrupt
DPV1: Update interrupt
DPV1: Vendor-specific interrupt
Diagnostic interrupt
Communication with the S7-300
5.2 DPV1 (X1 only as PROFIBUS DP interface)
5-5