Setting up an S7-300 with a Technology CPU
4.4 Subnets
4.4.2
Interfaces
MPI/DP interface
You can reconfigure this interface in STEP 7 as a PROFIBUS DP interface.
The MPI (Multi-Point Interface) represents the CPU interface for PG/OP connections, or for
communication on an MPI subnet.
The PROFIBUS DP interface is mainly used to connect distributed I/O. PROFIBUS DP
allows you to create large subnets, for example.
Interfaces
Table 4-3
MPI/DP interface (X1)
•
•
•
Which devices can you connect to which interface?
Table 4-4
MPI
•
•
•
•
4-4
Possible operating modes of interfaces on the Technology CPU
MPI
DP master
DP slave
Connectable devices
PG/PC
OP/TD
S7-300/400 with
MPI interface
S7-200
(with 19.2 kbaud only)
DP(DRIVE) interface (X3)
DP master for DP(DRIVE)
•
PROFIBUS DP
PG/PC
•
OP/TD
•
DP slaves
•
DP master
•
Actuators/sensors
•
S7-300/400 with
•
PROFIBUS
DP interface
DP (drive)
MICROMASTER 420/430/440 and
•
COMBIMASTER 411
SIMODRIVE 611 universal
•
SIMODRIVE POSMO CD/SI/CA
•
MASTERDRIVES MC/VC
•
ET 200M with IM 153-2 (isochronous!)
•
ET 200S with IM 151-1
•
SINAMICS S120 (optional with TM15
•
or TM17 high feature for high-speed
cams)
SIMODRIVE sensor isochronous
•
Analog drive interface ADI4
•
Tip: You will find a list of connectable
devices in STEP 7 under the "SIMATIC
Technology CPU" profile in the hardware
catalog.
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02