8.2

CPU 315T-2 DP

8.2
Technical data
Table 8-3
Technical data
CPU and version
Order no. [MLFB]
Technology objects
Memory
Working memory
Capacity of the retentive memory for retentive
data blocks
Load memory
Buffering
Data storage life on the MMC
(following final programming)
Execution times
Processing times of
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
Technical data for the CPU 315T-2 DP
Hardware version
Firmware version (CPU)
Firmware version (integrated technology)
Associated programming package
Total
Axes
Output cam
Cams
Measuring input
External encoders
Integrated
Expandable
Bit operations
Word instructions
Integer maths
Floating-point maths
6ES7 315-6TG10-0AB0
02
V 2.4
V 3.2
STEP 7 as of V 5.3 + SP 3 and option package
S7-Technology V3.0
32 (axes, cams, output cams, measuring inputs,
external encoders)
8 axes (virtual or real axes)
16 output cams
8 output cams can be output as "high-speed
output cams" on the integrated outputs of the
Technology CPU. A further 8 output cams can be
implemented via the distributed I/Os (e.g. on the
ET 200M or ET 200S). These can be implemented
as "high-speed output cams" on the TM15 and
TM17 High Feature.
16 cams
8 measuring inputs
8 external encoders
128 KB
No
Max. 128 KB
Plugged in with MMC (max. 8 MB)
Buffering guaranteed by MMC (maintenance-free)
At least 10 years
Typ. 0.1 µs
Typ. 0.2 µs
Typ. 2.0 µs
Typ. 3.0 µs
Technical data
8.2 CPU 315T-2 DP
8-3