9.2 ir33+ wide, ir33+ small wide, easy wide, easy small wide technical specifi cations
Power
Model
Voltage
PBEVxxExxxx
230 V~(+10/-15%), 50/60 Hz
supply
PBEVxxAxxxx
115 V~(+10/-15%), 50/60 Hz 115 V~(+10/-10%), 50/60 Hz (16 A, 8 A, 8 A version)
PBEVxxHxxxx
115/230 V~, 50/60 Hz
IREVxxLxxxx
12 to 24 V ~, 50/60 Hz, 12/30 Vdc
IREVxx0xxxx
12 V ~, 50/60 Hz, 12/18 Vdc
Insulation guaranteed
IREVxxExxxx
IREVxxAxxxxI-
by the power supply
REVxxHxxxx
IREVxxLxxxx
IREVxx0xxxx
Inputs
S1 (probe 1)
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
S2 (probe 2)
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
DI1
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
S3
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
DI2
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
S4
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
Maximum distance between probes and digital inputs less than 10 m
Note: in the installation it is recommended to separate the power and load connections from the probe, digital input, display and supervisor
cables.
Probe type
Std. Carel NTC
High temperature
NTC
Standard Carel PTC
Relay outputs depending on the model
Model
PBEVxx(E,A)(P,S,V,Y)xxx
PBEVxx(E,A)(N,C,A,L)xxx
PBEVxx(O,H)(N;C;A;L)xxx
PBEVxx(E,A)(P,S,V,Y)xxx
Insulation from extra low voltage parts
Insulation between independent relay
outputs
Connections
Cable cross-section from 0.5 to 2.5 mm2 max current 12 A
(*): Relay not suitable for fl uorescent loads (neon lights, etc.) that use starters (ballasts) with phase shifting capacitors. Fluorescent lamps with electronic controllers
or without phase shifting capacitors can be used, depending on the operating limits specifi ed for each type of relay.
The correct sizing of the power and connection cables between the instrument and the loads is the installer's responsibility. If using the controller at maximum
operating temperature and at full load, the cables used must be suitable for operation at least up to 105 °C.
Clock
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Front panel ingress protection
Environmental pollution
PTI of insulating materials
Period of stress across the insulating parts
Heat and fi re resistance category
Class of protection against voltage surge
Type of action and disconnection
Construction of the control device
Classifi cation according to protection against electric shock
Maximum distance between interface and display
Programming key
Safety standards: compliant with the relevant European standards
230 V~(+10/-10%), 50/60 Hz (16 A, 8 A, 8 A version)
insulation from extra low voltage parts
insulation from relay outputs
insulation from extra low voltage parts
insulation from relay outputs
10k at 25°C, range from –50T90°C
measurement error:
1°C in the range –50T50°C
3°C in the range +50T90°C
50kΩ at 25°C, range –40T150°C
measurement error:
1.5°C in the range –20T115°C
4°C in the range outside of -20T115°C
985Ω at 25°C, range from -50T150°C
measurement error
2°C in the range from –50T50°C
4°C in the range from +50T150°C
relay
5A(*)
8 A(*)
16 A(*)
2 HP
Reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
Basic, 3 mm clearance, 4 mm creepage, 1250 V insulation
reinforced, 6 mm clearance, 8 mm creepage, 3750V insulation
basic, 3 mm clearance, 4 mm creepage, 1250V insulation
to be guaranteed externally by safety transformer (SELV)
reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
EN60730-1
250 V~
operating cycles
5(1) A
100000
8(4)A N.O. 6(4)A
100000
N.C.2 (2)A N.O./N.C.
10(4)A N.O.(up to
100000
60°C) 12 (2) A
10(10)A
100000
error at 25°C ±10 ppm (±5.3 min/year)
error in the range -10T60°C -50 ppm (27 min/year)
-10T65°C for all versions
< 90% RH non-condensing
-20T70°C
< 90% RH non-condensing
Assembly on smooth and indeformable panel with gasket: IP65
2 (normal situation)
Printed circuits 250 and insulating materials 175
long
Category D and category B (UL 94 – V0)
Category II
1.B relay contacts (microswitching)
Built-in, electronic
Class II when appropriately integrated
10 m
Available on all models
47
Power
3 VA, 25mA ~ max
3 VA, 50mA ~ max
6 VA, 50mA ~ max
3 VA, 300 mA ~/ mAdc max
Only use SELV power supply
UL873
250 V~
operating
cycles
5A res. 1FLA 6 LRA C300
30000
8 A res. 2FLA 12 LRA C300
30000
12 A res. 5 FLA 30 LRA C300 30000
12 A res. 12 FLA 72 LRA
30000
ir33plus +0300028EN rel. 1.1 - 05.05.2017
ENG
Tab. 9.b

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ir33+Ir33+wideEasy wideEasy small wide

Table of Contents