5.1 Probes (analogue inputs)

The ir33+ platform controllers feature a maximum of 4 analogue inputs,
which are used for NTC, high temperature NTC (NTC Enhanced Range)
or PTC temperature sensors (see the note below). Probes S3 and S4 can
also be confi gured as digital inputs. Probe S1 is the control probe and its
function cannot be changed; the functions of probes S2, S3, S4 can be
selected using parameters /A2, /A3, /A4. The probes can be calibrated
to adjust their readings. In particular, parameters /c1 to /c4 are used to
increase or decrease the values read by the probes connected to inputs
S1, S2, S3 and S4 across the entire the range of measurement. For the
calibration procedure, see paragraph 3.5.
Par. Description
/P
Type of probe
0 = NTC Standard Range -50T90°C
1 = NTC Enhanced Range -40T150°C
2 = PTC Standard Range -50T150°C
/c1
Probe 1 calibration
/c2
Probe 2 calibration
/c3
Probe 3 calibration
/c4
Probe 4 calibration
T2
A
min
Key
T1
Temperature read by the probe
T2
Value calibrated by T1
A
Calibration value
min, max
Range of measurement
Note: the controllers that use PTC probes may have diff erent part
numbers from those that only use NTC probes.
Example:
Model
P/N
ir33+
IREV*7*******
ir33+ wide
PBEV*6*******
easy wide
Assigning the functions of probes S2, S3, S4
The controller, inside the refrigerated cabinet or cold room, can use the
following probes:
defrost, located on the evaporator, preferably where ice remains the
longest;
condenser, used to protect the compressor against high pressure
when the condenser is off or the condenser fan is malfunctioning;
frost protection, to activate the corresponding alarm.
Note:
to confi gure probes 3 and 4 as digital input 1 and 2 respectively, set
parameters /A3 e /A4 =0;
if multiple probes have been confi gured with the same operating
mode, the controller will use the fi rst probe in increasing order with
that confi guration.
ir33plus +0300028EN rel. 1.1 - 05.05.2017

5. FUNCTIONS

Def Min Max UOM
0
0
2
0
-20
20
0
-20
20
0
-20
20
0
-20
20
Tab. 5.a
T1
max
Fig. 5.a
Probes available
NTC/PTC
PTC
Tab. 5.b
Par. Description
/A2 Probe 2 confi guration (S2) (M models)
/A2 Probe 2 confi guration (S2)
0 Absent
1 Product (display only)
2 Defrost
3 Condenser
4 Frost
/A3 Probe 3 confi guration (S3)
0 Digital input 1 (DI1)
1 Product (display only)
2 Defrost
3 Condenser
4 Frost
-
/A4 Probe 4 confi guration (S4/ DI2)
0 Digital input 2 (DI2)
1 Product (display only)
2 Defrost
-
3 Condenser
-
4 Frost
-
-

5.2 Digital inputs

Digital inputs DI1 and DI2 respectively can be enabled in the place of
probes S3 and S4. Digital inputs 1, 2 must fi rst be enabled (par. /A3 and /
A4 = 0) and then assigned to a specifi c function (par. A4 and A5). Finally,
an external contact can be connected to the multifunction input to
activate various types of functions, such as alarms, curtain/door switches,
start defrost, etc. See the table below.
Important: to ensure unit safety in the event of serious alarms, the
unit must be fi tted with all the electromechanical safety devices needed
to guarantee correct operation..
Note: (applies to all settings of par. A4 and A5): if 2 digital inputs are
confi gured in the same way, for example to enable defrost, the disable
event is generated when at least one of the inputs is open, while the
enable event is generated when at both inputs are closed.
Digital input functions
Setting
0 = not active
1 = immediate external alarm
2 = delayed external alarm
3 = select probe (ir33M)
3 = enable defrost (all other models)
4 = start defrost
5 = door switch with compressor and evapo-
rator fans off
6 = remote ON/OFF
7 = curtain switch
8 = low pressure switch
9 = door switch with fans off
10 = direct/reverse operation
11 = light sensor
12 = activate aux output
13 = door switch with compressor and fans
off and light not managed
14 = door switch with fans off and light not
managed
24
Def Min Max UOM
0
0
2
0
0
0
0
0
PARAMETERS A4, A5
Contact
OPEN
-
-
active
not active
active
not active
see /tI
fi rst probe
enabled (/A2,
/A3, /A4, /A5)
not enabled
enabled
not active
active
door open
door closed
OFF
ON
curtain open curtain closed
low pressure
normal status
status
door open
door closed
direct mode
reverse mode
light off
light on
deactivated
activated
door open
door closed
door open
door closed
4
-
4
-
3
-
4
-
Tab. 5.c
CLOSED
Tab. 5.d