SITRANS F C MASSFLO
5.2.1
The
eter. The menu structure is valid for the title and subtitle line only. The upper line is for primary
The menu is built up in two parts. An
The operator menu is for daily operation. The operator menu is customised in the
setup. The transmitter always starts in the
backward keys are used to step through the operator menus.
The setup menu is for commissioning and service only.
Access to the setup menu is gained by pressing the top up key for 2 seconds. The setup menu will
operate in two modes:
View mode
Setup mode
is a read only mode. The pre-selected settings can only be scanned.
is a read and write mode. The pre-selected settings can be scanned and changed.
Access to the setup mode is protected with a password. The factory set password is 1000.
Access to a submenu in the set up menu is gained by the lock key. A short press on the top up
key will bring you back to the previous menu. A long press (2 sec.) on the top up key will exit the
setup menu and bring you back to the operator menu no. 1.
(Read only)
(Read and write mode)
Access to view mode is always gained by pressing the forward key when in the password menu.
Access to change mode is protected by a user code. The user code is factory set to 1000, but can
be changed to any value between 1000 and 9999 in the change password menu.
The factory setting of 1000 can be re-established as follows:
Switch off power suppply
The user code is now reset to 1000.