Siemens SITRANS F MASS 6000 Ex d Operating Instructions Manual page 10

Coriolis flowmeters
Hide thumbs Also See for SITRANS F MASS 6000 Ex d:

Advertisement

SITRANS F C MASSFLO
Directives
MASS 6000 Ex-d
0539
II 2 G
DEMKO 03 ATEX 135253X
Ex d e ib [ia Ga] IIC T4 Gb
ambient temperature 20 to +50 C/ 4 F to 122 F
EN 60079-0:2012+A11:2013
EN 60079-1:2007
EN 60079-7:2007
EN 60079-11:2012
EN 60079-25:2010
For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds1% of
the Co and Lo parameters of the MASS 6000 (excluding the cable), then 50% ofCo and Lo
parameters are applicable and shall not be exceeded. The reduced capacitanceshall not be
greater than 1 μF for Groups IIB and IIA, and 600 nF for Group IIC.
If the sensor, to which MASS 6000 is connected, measures liquids with temperatureabove
50 °C (122 °F), the MASS 6000 must be thermally insulated or separately installed.
The 24 V supply voltage shall be from a safety-isolated transformer according to EN 60742
All the wiring for increased safety shall be in the separate section of the terminal compart-
ment and shall be covered with the plastic cover. The cover is marked with "Increased
Safety".
The transmittershall always be connected to PE (earth ground) using the internalterminal or
the external PE (earth ground).
The equipment shall either be installed in an area where there is a low risk of mechanical
damage or, if this not possible, the window shall be protected with an additional guard that
provides it with mechanical protection adequate for the application.
The equipment must be protected against direct sunlight and other ultraviolet light sources.
A5E02944883-A
/ 24-14 AWG.