Download Print this page
Siemens SITRANS F MASS 6000 Ex d Operating Instructions Manual
Siemens SITRANS F MASS 6000 Ex d Operating Instructions Manual

Siemens SITRANS F MASS 6000 Ex d Operating Instructions Manual

Coriolis flowmeters
Hide thumbs Also See for SITRANS F MASS 6000 Ex d:

Advertisement

Quick Links

SITRANS F
Coriolis Flowmeters
MASS 6000 Ex d transmitter
Operating Instructions
Edition
12/2015
Answers for industry.

Advertisement

loading

Summary of Contents for Siemens SITRANS F MASS 6000 Ex d

  • Page 1 SITRANS F Coriolis Flowmeters MASS 6000 Ex d transmitter Operating Instructions Edition 12/2015 Answers for industry.
  • Page 3 These Operating Instructions apply to Siemens products SITRANS MASS 6000 Ex d with order code commencing 7ME4110-2G, 7ME4110-2H, 7ME4110-2J. For use with sensor type MASS 2100 or FC300. /2015 A5E02944883-...
  • Page 4: Table Of Contents

    Introduction ......................... 4 Installation ........................5 Compact ........................6 Remote ........................6 Ex survey according to Directive 94/9/EC (ATEX) ............6 Overview ........................7 ..................... 8 Approvals ........................9 Special conditions for safe use of MASS 6000 Ex-d version and MASS 2100 ....9 Mounting of transmitter compact or remote ...............
  • Page 5: Installation

    Installation of the equipment must comply with national regulations. Example EN 60079-14 for Denmark. Repair and service can be done by approved Siemens Flow Instruments personnel only. The p/T ratings indicate the relationship between the maximum allowable pressure PS and the maximum allowable temperature.
  • Page 6 SITRANS F C MASSFLO Transmitter MASS 6000 Ex-d may Horizontal mounting Mount the sensor on a vibration-free wall or steel frame as shown. Ensure that the sensor is not emptied of liquid (during normal operation) otherwise incorrect measurement will occur. Vertical mounting Locate the sensor low in the system in order to avoid an under-pressure in the sensor sepera-...
  • Page 7 SITRANS F C MASSFLO as an example Applies to instruments used in underground mining operations, as well as their above ground operations, which can be endangered by mine gas and/or flammable dusts. Applies to instruments used in the remaining areas which can be endangered by a potentially explosive atmosphere.
  • Page 8: Compact

    SITRANS F C MASSFLO A = Ex e (Increased safety) B = Ex ia (Intrinsic safety) MASS 6000 Ex-d Flameproof enlosure C = Ex d (Flameproof safety) Ex d e ib [ia Ga] IIC T4 Gb 1. M20x1.5, black ATEX approved glands, power supply cable.
  • Page 9 User Tag No. : XXXXXXXX Warning - Do not open when energized After de-energizing, wait 30 minutes before opening Siemens A/S Flow Instruments, 6400 Soenderborg, Denmark Made in France Explosion protected ATEX Equipment Group and Protection Category EC Approval Numbers and Protection Type...
  • Page 10 SITRANS F C MASSFLO 0539 II 2 G DEMKO 03 ATEX 135253X Ex d e ib [ia Ga] IIC T4 Gb ambient temperature 20 to +50 C/ 4 F to 122 F Directives EN 60079-0:2012+A11:2013 EN 60079-1:2007 EN 60079-7:2007 EN 60079-11:2012 EN 60079-25:2010 For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds1% of the Co and Lo parameters of the MASS 6000 (excluding the cable), then 50% ofCo and Lo...
  • Page 11: Remote

    SITRANS F C MASSFLO For compact installation mount the transmitter on top of the sensor interface. Please make sure that it is correctly oriented (note the little Compact Ex-d version tap). The transmitter is fastened with 4 allen screws (Allen key M4). Remote Ex-d version For mechanical mounting refer to instruction 083R9504 supplied with the mounting kit.
  • Page 12 SITRANS F C MASSFLO Turn off the power supply before connecting input and output cables and wait 30 minutes before unscrewing the lid. Mounting and connection View A Ex e M20 black ATEX Ex-e approved gland, power supply cable "e". Earthing terminal connected to potential equalisation rails (PEC).
  • Page 13 SITRANS F C MASSFLO (continued) Important Electrical connections are made through the front of the transmitter (view A), in the terminal housing. This housing is accessed by removing the front cover described in chapter 2. Read the chapter 4. "Technical data" before making the connection. The cover is retained via a wire.
  • Page 14 SITRANS F C MASSFLO The current output in MASS 6000 can operate in either active or passive mode to make electrical connection as easy as possible. The current output in MASS 6000 is default set to active mode. View C Ex d transmitter PCB must be put in passive position.
  • Page 15 SITRANS F C MASSFLO the equipment from the supply circuits and wait 30 min. for dischanging the energy in the internal electronics before opening. View C Remove the rear cover, by loosening the safety Ex d tap allen screw (M3) and turn the rear cover counter-clockwise.
  • Page 16 SITRANS F C MASSFLO Current output in passive mode Frequency/pulse output in passive mode HART output Intrinsically safe data "ia", please look into the "Technical data" in chapter 4. A5E02944883-A...
  • Page 17 SITRANS F C MASSFLO MASS 6000 Ex-d (lb/ft ], temperature [ C ( F)] Current 0-20 mA or 4-20 mA Load 350 ohm Time constant Active mode (read note 1) Passive mode (max. input from external barrier) (Terminals: 31-32) 30 V 74 mA 100 mA 0.45 W...
  • Page 18: Approvals

    5 or [ H/ ] [nF] 1410 1410 Cable between sensor and Maximum distance between sensor and transmitter MASS 6000 is 300 m with Siemens Flow MASS 6000 Instruments cable FDK:083H3005 or FDK:083H3006 or equivalent cable. Cable data Capacitance 300 [pF/m]...
  • Page 19 SITRANS F C MASSFLO Intrinsic safe terminals in the connections room are in general evaluated as „ia“ for gas group IIC. The output terminals 31-32 is set in „active mode“ which means that it can be connected to other the note 1. When the terminal 31-32 is in „active mode“...
  • Page 20 SITRANS F C MASSFLO MASS 6000 Ex-d Power supply off Power supply on No error Error 1 set point 2 set points A5E02944883-A...
  • Page 21 SITRANS F C MASSFLO Keypad This key (hold 2 sec.) is used to switch between operator menu and setup menu. In the transmitter setup menu, a short press will cause a return to the previous menu. FORWARD KEY This key is used to step forward through the menus. It is the only key normally used by the operator.
  • Page 22 SITRANS F C MASSFLO eter. The menu structure is valid for the title and subtitle line only. The upper line is for primary The menu is built up in two parts. An and a The operator menu is for daily operation. The operator menu is customised in the setup.
  • Page 23 SITRANS F C MASSFLO A5E02944883-A...
  • Page 24 SITRANS F C MASSFLO Basic settings menu open the respective window. selected. Select units (moving the cursor) by means of the SELECT KEY A5E02944883-A...
  • Page 25 SITRANS F C MASSFLO Current output The current output must be set off when not used. Digital output Pulse Digital output Frequency A5E02944883-A...
  • Page 26 SITRANS F C MASSFLO Digital output Batch Error level (Also possible through digital output) Acceptance level is set in the basic settings menu. Error number (Also possible through digital output) Limit switch & direction switch (Also possible through digital output) A5E02944883-A...
  • Page 27 SITRANS F C MASSFLO made automatically where the meter measures and calculates the correct 0-point. In manual mode the 0-point can be programmed if this is known. Normally the is used. of 30 sec. is used which normally is enough for a stable 0-point mesurement. If however the can be selected, to obtain a better 0-point measurement.
  • Page 28: Sensorprom Unit

    SITRANS F C MASSFLO Power on has activated Active Active Applied A new module has been added to the system Active Active An add-on module is defect or has been removed. Install This can also be an internal add-on module Active Active A less vital parameter in the transmitter has been re-...
  • Page 29 SITRANS F C MASSFLO Symptom Output Error Cause Remedy MASS 6000 Ex-d signals code Minimum 1. Supply voltage 1. Check supply voltage 2. MASS 6000 defective 2. Replace MASS 6000 Minimum 1. Current output deselected 1. Activate current output 2. Digital output deselected 2.
  • Page 30 SITRANS F C MASSFLO MASS 6000 transmitter 1 current output 24 V AC/DC Ex-d inclusive wall 1 frq./pulse output mounting kit with 5 m 1 relay output (16.4 ft) sensor cable MASS 6000 transmitter 1 current output 24 V AC/DC Ex-d inclusive wall 1 frq./pulse output mounting kit with 10 m...
  • Page 31: For More Information

    For more information www.siemens.com/flow Siemens A/S Subject to change without prior notice Flow Instruments Order No.: A5E02944883 Coriolisvej 1-3 Lit. No.: A5E02944883-AB DK-6400 Soenderborg © Siemens AG 12/2015 A5E02944883 www.siemens.com/processautomation...