View/Set Unit – Keypad/Display Menu Structure
Figure 118 continued:
View/Set Unit
Unit Status/Settings
Occupancy
Temperatures
Flow Status
SAF Spd Control
RF/EF Control
Cooling
Economizer
Min OA Damper
Heating
Dehumidification
Date/Time/Schedules
Unit Status/Settings
Occupancy
Unit State= ___________
Occupancy= __________
Unit Status= __________
Occ Mode= Auto/Net
MWU Status= _________
OccSrc= _____________
Dehum Status= ________
UnoccSrc= ___________
Ctrl Mode= Off
Tnt Ovrde Tm= 0 min
Clg Status= ___________
Htg Status= ___________
SuplHtgStatus= ________
Econo Status= _________
Clg Capacity= XXX%
Htg Capacity= XXX%
Supl Htg Cap= XXX%
Reheat Cap= XXX%
SAF Speed= XXX%
RF/EF Cap= XXX%
OAD/Econo Cap=XXX%
Rel Humidiy= XXX%
Net Emrg Ovrd= Normal
Net App Mode= Auto
IM 893-10 • ROOFPAK SINGLEZONE UNITS
Temperatures
Flow Status
Control Temp= XXX°F
Airflow= ______________
Disch Temp= XXX°F
Waterflow= ___________
Return Air= XXX°F
Water Pump= _________
Space Temp= XXX°F
Supply Fan= __________
OA Temp= XXX°F
Ret/Exh Fan= _________
EF/LC Temp= XXX°F
EW Temp= XXX°F
Mixed Air= XXX°F
ER LAT= XXX°F
ER EAT= XXX°F
Sump Temp= XXX°F
PA Temp= XXX°F
DRT1= XXX°F
DRT2= XXX°F
DRT3= XXX°F
SRT= XXX°F
DFT= XXX°F
IRT= XXX°F
ORT= XXX°F
INVCompTemp= XXX°F
116
k
/d
M
s
eyPad
IsPlay
enu
SAF Speed Control
RF/EF Control
SAF Speed= XXX%
RF/EF Cap= XXX%
Speed Cmd= XXX%
Speed Cmd= XXX%
Duct Press= X.Xin
Bldg Press- X.XXin
DuctSP Spt= 1.0in
BldgSP Spt= 0.050in
IAQ PPM= XXXXPPM
OA Flw= XXXXXCFM
MinOAFlw Spt= 2000CFM
Bldg Press= X.XXin
BldgSP Spt= 0.05in
www.DaikinApplied.com
TruCTure