5. Operating the appliance
Installer level - #SECONDARY INSTAL.P menu
Parameter
Adjustment range
ADAPT
ON
OFF
(6)
TOTAL
PRIORITY DHW
SLIDING
NO
LEG PROTEC
OFF
DAILY
WEEKLY
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f
(3) The parameter is only displayed if SCREED DRYING is other than OFF
(4) According to the configuration
(5) The parameter is only displayed if IN 0-10V is set to ON.
(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
Installer level - Menu #SOLAR
Parameter
DEC.SOLAR DHW
REFERENCE DT
MAX.T.COLLECTOR
MAX TPS PUMP
MIN.PUMP SPEED
TUBULAR COLLECTOR YES / NO
MAX FLOW
(1) The menu is only displayed if the solar control system is connected and the INSTALLATION parameter is set to EXTENDED
49
Description
Automatic adaptation of the heating curves
for each circuit with a room sensor with an
influence of >0.
The heating curves can only be modified
manually.
Interruption of pool heating and reheating
during domestic hot water production.
Domestic hot water production and heating
on the valve circuits if the available output
is sufficient and the hydraulic connection
allows.
Heating and domestic hot water production
in parallel if the hydraulic connection allows.
a Risk of overheating in the direct circuit.
The anti legionella function acts to prevent
the development of legionella in the dhw
tank, these bacteria are responsible for
legionellosis.
Antilegionella function not activated
The tank is overheated every day from
4:00 o'clock to 5:00 o'clock
The tank is overheated every Saturday from
4:00 o'clock to 5:00 o'clock
(1)
Adjustment range Description
0 to 30 °C
Maximum drop in the DHW set point when
the solar pump is running at 100%
10 to 20 °C
Temperature difference that the solar
pump tries to maintain between the solar
DHW sensor and the panel
100 to 125 °C
Temperature of the panel above which
the solar pump starts up.
The pump does not operate if the
temperature of the solar tank is higher
than 80°C
1 to 5 min
Minimum operating duration of the solar
pump at 100% on start-up
50 to 100 %
Minimum speed of the solar pump
Set to YES if tubular collectors are used
0 to 20 l/min
Maximum flow rate of the solar pump
¼ "MAX FLOW", page 52
iSense Pro DIN - AD280
Factory
Customer
setting
setting
ON
TOTAL
OFF
Factory
Customer
setting
setting
5°C
10°C
100°C
1 minute
50%
NO
6.7 l/mim.
22/11/2012 - 300025649-001-01