iSense Pro DIN - AD280
Settings to be made for this type of installation
Parameters
INSTALLATION
MAX. CIRC. B
(1)
CIRC. B:
If a heating shutdown command
is connected to the 0-10V inlet
on the terminal block:
IN 0-10V
If a heating shutdown command
is connected to the 0-10V inlet
on the terminal block:
(2)
I.TEL:
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
22/11/2012 - 300025649-001-01
Access
Installer level
Menu #SYSTEM
Installer level
Menu #SECONDARY
LIMITS
Installer level
Menu #SYSTEM
Installer level
Menu #SYSTEM
Installer level
Menu #SYSTEM
n Controlling the pool circuit
The control system can be used to manage a swimming pool circuit
in both cases:
Case 1: The control system regulates the primary circuit (boiler/
exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to the
pump B outlet. The temperature MAX. CIRC. B is then guaranteed
during comfort periods on programme B in summer and winter
alike.
4 Connect the pool sensor (package AD212) to the S OUTL B input.
4 Set the set point of the pool sensor using key C in the range 5 -
39°C.
Case 2: The pool has already a regulation system that is to be
kept. The control system only regulates the primary circuit
(boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to the
pump B outlet.
The temperature MAX. CIRC. B is then guaranteed during comfort
periods on programme B in summer and winter alike.
Settings to be made
EXTENDED
Set the value of MAX.
CIRC. B to the
temperature
corresponding to the
needs of the exchanger
SWIM.P.
NO
0/1 B
The swimming pool can also be connected to circuit C by
adding the AD249 option:
Make the connection to the terminal blocks marked
4
C.
Set the parameters for circuit C.
4
4. Installation
See chapter
¼ "Displaying the parameters
in extended mode", page 38
¼ "Professional settings",
page 46
¼ "Setting the parameters
specific to the installation", page
38
26