Install the System

Complete the following steps to install the CompactLogix 5370 L1
control system.

Mount the System

Ground the System

Install the Controller

Connect Power to the Controller (Series B)
series B controllers, and series A L19ER
Mount the System
You mount a CompactLogix 5370 L1 control system on a DIN rail. Before you
complete the steps that are required to install the system, install a DIN rail.
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring
method that complies with the governing electrical codes.
Before you mount a CompactLogix 5370 L1 control system, consider
the following requirements:
Available DIN Rails
Minimum Spacing
System Dimensions
Available DIN Rails
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding.
The use of other DIN rail materials (for example, aluminum or plastic) that
can corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.
You can mount the CompactLogix 5370 L1 controller on the following
DIN rails:
• EN 50 022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.)
Rockwell Automation Publication 1769-UM021G-EN-P - October 2015