Camus Hydronics DMH 081 Installation, Operation And Service Manual page 9

Dynamax series gas fired wall hung & floor mount residential commercial stainless steel boilers
Table of Contents

Advertisement

Input [BTU/hr]
80,000
100,000
150,000
200,000
250,000
Depth Dim.
Input
[BTU/hr]
"A" [in.]
80,000
16 1/2
100,000
16 1/2
150,000
16 1/2
200,000
23 1/2
250,000
23 1/2
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance
Table 3: DynaMax Wall Hung Service Clearances
Front
Top
24" (61cm)
0" (0 cm)
24" (61cm)
0" (0 cm)
24" (61cm)
0" (0 cm)
24" (61cm)
0" (0 cm)
24" (61cm)
0" (0 cm)
Figure 3: DynaMax Wall Hung Model Dimensions
Table 4: Appliance Dimensions and Specifications
Equivalent Length of Vent & Air
Intake Pipes at Recommended
Dim.
"B"
Over 25'
[in.]
and up to
100'
12
3
12
3
12
3
19
3
19
3
Service Clearance, Inches (cm)
Right Side
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
Diameter, [in.]
Over 15'
Up to 15'
and up to
25'
3
2
3
2
3
2
3
2
3
2
Left Side
Rear
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
0" (0 cm)
Water
Gas Conn. At
Conn [in.]
Boiler [in.] NPT
NPT
1
1/2
1
1/2
1
1/2
1
1/2
1 1/4
1/2
5

Advertisement

Table of Contents
loading