Cleaning Work - Defensor PH27 Operating Instructions Manual

Adiabatic humidifiers
Hide thumbs Also See for PH27:
Table of Contents

Advertisement

30
6.2.2

Cleaning work

Unit component
Base tub
Rotary humidification drum
Evaporator mat
Air intake and air outlet lattices
Coarse dust filters (Quattro filters)
What to clean and how to clean
• Wash parts with a lukewarm soap solution and rinse
well with tap water.
• Occasionally remove scale coating with a household
decalcify agent (observe safety notes in chapter 6.6).
Finally rinse the parts well with tap water.
• Rinse the evaporator mat thoroughly with lukewarm
water without any additives.
Note: As soon as the filter replacing message appears
in the display (see error messages in chapter 7) replace
the
evaporator mat
together with the coarse dust filters
(Quattro filters).
• Clean the air intake and air outlet lattices on both sides
with a vacuum cleaner.
• Clean the coarse dust filters (Quattro filters) on the inner
side with a vacuum cleaner (lowest power step).
Note: As soon as the filter replacing message appears
in the display (see error messages in chapter 7) replace
coarse dust filters (Quattro filters) together with the
evaporator mat
evaporator mat.
Make sure the filters do not get wet. Wet
CAUTION!
filters must be dry before reinstalling.