6.5

Resetting the filter changing message

After the replacement of the filters and the evaporator mat the filter changing message can be reset
as follows:
Warning 6
Filter change
Filter change
ESC
1. Switch on the unit (the filter changing message appears).
2. Press the <ESC> and <Enter> keys simultaneously until the opposite
message appears.
OK
3. Press the <Enter> key to reset the filter changing message and the
interval counter. The standard operating display appears.
Note: By pressing the <ESC> key the reset procedure can be can-
celled without action. The filter changing message is then displayed
again.