7

Fault elimination

7.1

Event messages

Display
Radio hygro. K1
Install.? ESC/E
Radio hygro. K1
Test
7.2

Warning messages

Display
Warning 6
Filter change
Warning message is alter-
nating with the standard
operating display.
Cause:
Action/Remedy: Replace filter set (see chapter  "Maintenance"), then reset warning message.
Warning 7
No water
Warning message is dis-
played until the water level in
the base tub is ok. again.
Note:
Cause:
Action/Remedy: Check/refill water tank.
Warning 8
Battery radio
Warning message is alter-
nating with the standard
operating display.
Cause:
Action/Remedy: Replace battery of the radio humidistat (see separate instructions of radio humidistat).
Description
Cause:
Action:
Cause:
Action:
red LED
lights
Maximum lifetime of the filter set expired.
lights
This message is displayed only on the Defensor PH27
The water level in the base tub is too low, level switch has triggered.
lights
Battery in radio humidistat (option) is empty.
If a new battery is inserted into the radio humidistat (option)
and the radio channel of the humidistat does not correspond to
the active channel of the Defensor PH27/PH27A a beep sounds
briefly (if the buzzer is activated) and a new radio channel (e.g.
K1) will be proposed.
Press the <Enter> key if you want to confirm the suggested
channel. The Defensor PH27/PH27A switches to the new chan-
nel and returns to the standard operating display.
Press the <ESC> key if you want to reject the suggested
channel. The Defensor PH27/PH27A returns to the standard
operating display and uses the old signal source.
If a new battery is inserted into the radio humidistat (option)
and the radio channel of the humidistat does correspond to the
active channel of the Defensor PH27/PH27A a beep sounds
briefly (if the buzzer is activated) and the unit confirms the cor-
rect channel.
To reset the message and to return to the standard operating
display press the <Enter> or the <ESC> key.
Buzzer
Error relay
–––
activated
–––
activated
beeps
briefly
activated
every 30 min-
utes
3
Resetting
see chapter ..
Automatic resetting as
soon as the water level
in the base tub is at normal
level again.
Automatic resetting af-
ter replacement of the
battery.