Understanding Signal
Specifications
IOL Pin
Signal
Description
Line contactor coil connections with an auxiliary contact from the control
IOL-8
COIL_E2
power circuit breaker wired in series with the contactor coil. The line
IOL-7
COIL_E1
contactor is a safety contactor that includes three main contacts with three
auxiliary contacts (see the figure on
IOL-12
ALRM_COM
Non-voltage contact (ALRM_M) to indicate that CB1 is closed (make) when
CB1 is tripped. (DC)
Non-voltage contact (ALRM_B) to indicate that CB1 is closed (make) when
CB1 is not tripped.
IOL-9
ALRM_M
See the figure on
IOL-11
ALRM_B
[AC]
[AC]
IOL-14
CONSTAT_12
IOL-13
CONSTAT_11
IOL-16
CONSTAT_22
Three safety-rated auxiliary contacts that are normally-closed on the line
IOL-15
CONSTAT_21
contactor (see the figure on
IOL-18
CONSTAT_32
IOL-17
CONSTAT_31
IOL-20
CONSTAT_54
One auxiliary contact (normally-open) that is not safety rated and should
IOL-19
CONSTAT_53
not be used in a safety string.
IOL-2
IOL-4
IO_COM1
Power supply capable of supplying 24V @ 20 A for I/O functions and
IOL-6
switches. Each set of pins is capable of 8 A. To use the full rating of the
supply, all pins must be used to provide the appropriate current rating (see
IOL-1
the figure on
IOL-3
IO_PWR1
IOL-5
A description of the I/O (IOL), brake power (P1L/PSL), control power (CPL),
and auxiliary power (P2L) signals and circuit specifications is provided on the
following pages.
See the
Block Diagrams
schematic.
I/O Signals
The 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx line interface module I/O
(IOL) signals include the contactor coil, alarm contacts, status contacts, and I/O
power supply.
This table provides a description and electrical specifications for the IOL
connector signals. See
specifications.
Table 13 - IOL (21-pin) Signal Specifications
(catalog numbers 2094-AL S, 2094-BL S, and 2094-XL75S-C )
page
19).
page
18. (DC)
page
20).
page
21).
Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
beginning on
page 45
for your line interface modules
Power Specifications
on
page 52
Voltage (Volts)
Min
Nom
18
24
—
—
—
—
—
—
—
24
21.6
24
Line Interface Module 17
for auxiliary contactor
Current (Amps)
Max
Min
Nom
Max
30
0.005
0.011
0.017
125
—
—
1
250
—
—
5
600
—
—
2
—
—
—
10
26.4
—
—
8