HID VertXHID V2000 Quick Installation Manual page 7

Reader interface / access controller
Table of Contents

Advertisement

VertX V2000 (CS) Quick Installation Guide
3. Reader Connections: Connect
Wiegand or clock-and-data interfaces
using the connection table shown. You
can connect up to 10 signal lines for
the reader. Use as many signal lines
as are required for your reader
interface.
Note: Connect the data return line to
the same ground as the reader power,
if the reader is not powered by the
VertX controller's 12VDC.
4. Output Connections – All Output connections are used for
general purpose controls. The following table shows where the
various outputs are located among the various VertX types. Pin
numbers shown use the convention "NO/C/NC". For example,
Output 1, V2000: P3 Pin1 is NO (Normally Open) and Pin 2 is
C (Common) and Pin 3 is NC (Normally Closed).
Note: Relay contacts are rated for 2Amps @ 30VDC.
Output
number
P3 Pins 1/2/3
1
Strike (lock)
Relay 1
P3 Pins 4/5/6
2
Aux Relay 1
P6 Pins 6/5/4
3
Strike (lock)
Relay 2
P6 Pins 3/2/1
4
Aux Relay 2
5
6
7
8
9
August 2005
V2000
V1000
P14 Pins 2/3/4
P11 Pins 6/5/4
2005 © HID Corporation. All rights reserved.
Pin #
V2000 P1
1
Reader Power
2
Ground
Data 0 / Data
3
4
Data 1 / Clock
5
Data Return
6
Green LED
7
Red LED
8
Beeper
9
Hold
10
Shield Ground
V100
V200
P3 Pins 1/2/3
P3 Pins 2/3/4
Strike (lock)
Relay 1
P3 Pins 4/5/6
P6 Pins 3/2/1
Aux Relay 1
P6 Pins 6/5/4
Strike (lock)
Relay 2
P6 Pins 3/2/1
Aux Relay 2
V2000 P4
Shield Ground
Hold
Beeper
Red LED
Green LED
Data Return
Data 1 / Clock
Data 0 / Data
Ground
Reader Power
V300
P1 Pins 1/2/3
P1 Pins 4/5/6
P1 Pins 7/8/9
P2 Pins 1/2/3
P2 Pins 4/5/6
P2 Pins 7/8/9
P4 Pins 9/8/7
P4 Pins 6/5/4
P4 Pins 3/2/1
Page 7 of 23