Electric power remains in the capacitors even the power supply is shut off. Do not forget to discharge the electricity power in the capacitor.
Electric Capacitors
(HIGH VOLTAGE! CAUTION!)
Fig. 22 – Electrolytic Capacitors
For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, − terminals of the electrolytic
capacitor on the contrary side of the outdoor PCB.
Fig. 23 – Discharging Position
NOTE: Fig 23 is for reference only. The plug associated with your unit may differ.