Ruffneck AH-12A Owner's Manual

Advanced horizontal series heat-exchanger unit heaters

Advertisement

Available languages

Available languages

Quick Links

®
ISO 9001
Owner's Manual
Advanced
Horizontal
Series
Heat-Exchanger Unit Heaters
APPROVED LOCATIONS
The Forced Air Heaters are CSA listed,
certified for the following locations:
Class I, Divisions 1 & 2, Groups C & D;
Class II, Division 1 & 2, Groups E, F, & G;
Class III, Division 1 & 2;
Temperature Code T3B 329˚F (165˚C)
(On Applicable Models Only)
For details of hazardous locations with potential for
explosion, refer to the Canadian Electrical Code, Part 1,
Section 18 or National Electrical Code articles 500-516.
This manual covers installations, maintenance, repair and replacement parts.
WARNING!
READ ALL IMPORTANT NOTICES ON PAGE 3.
PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.
Failure to do so may be dangerous and may void certain provisions of your warranty.
Ruffneck™ is a key brand of CCI Thermal Technologies Inc.
Copyright © 2015. All rights reserved.
Issue Date: April 2015
5475.Rev.9.02
Printed in Canada
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AH-12A and is the answer not in the manual?

Questions and answers

Summary of Contents for Ruffneck AH-12A

  • Page 1 PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL. Failure to do so may be dangerous and may void certain provisions of your warranty. Ruffneck™ is a key brand of CCI Thermal Technologies Inc. Copyright © 2015. All rights reserved. Issue Date: April 2015 5475.Rev.9.02...
  • Page 2: Heater Maintenance Checklist

    Photocopy HEATER MAINTENANCE CHECKLIST this page for reuse. For Heat-Exchanger Unit Heaters Heater Model: Serial No.: Date of Maintenance: Maintenance Done By: Comments: WARNING! Heater should only be serviced by qualified personnel with heating equipment experience. Disconnect heater from power supply before servicing heater. Lock the switch in the “OFF”...
  • Page 3: Important Notices

    IMPORTANT NOTICES WARNING! IMPORTANT NOTICES Read and adhere to the following. Failure to do so may result in severe or fatal injury. Read and follow the instructions in this manual. WARNING: For steam service use only single-pass models. Refer to model coding (page 7) for number of passes in heat exchanger.
  • Page 4: Mounting Clearances

    1/2” (14 mm) bolts. For heater dimensions, see For ease of installation, a variety of mounting kits are Figure 2 for single fan or Figure 3 for 24” tandem. available from the factory. AH-12A AH-16A AH-20A AH-24A MOUNTING HEIGHTS 15-13/16 19-13/16 23-13/16 27-7/8...
  • Page 5 PIPING APPLICATIONS PIPING APPLICATIONS For steam service use only single-pass heaters. Refer to For steam service use only single-pass heaters. Model Coding Section for tube-side pass designation. Refer to Model Coding Section for tube-side pass Refer to figures 4-6 for typical piping applications. designation.
  • Page 6: Motor Wiring Diagrams

    CAUTION MOTOR WIRING DIAGRAMS Installation must be done by qualified personnel, and comply with local electrical codes. MOTOR WIRING DIAGRAMS For internal wiring of control devices and starters, CAUTION consult device manufacturer. The thermostat must have an electrical rating CAUTION equal to or exceeding the rating of the control device.
  • Page 7: Model Coding

    Heresite® phenolic coated carbon steel  NOTE: CONNECTIONS Ruffneck™ utilizes Doerr/Emerson/Baldor as our standard 1½” NPT Male Sch. 40 motor. Specifying any other O.E.M. motor may result in longer lead times. All heat exchangers are registered to CRN 1½” (40 mm) 300# RF flange OH10951.2C.
  • Page 8: Repair And Replacement

    REPAIR & REPLACEMENT REPAIR & REPLACEMENT Core Bolts WARNING Heater should only be serviced by qualified W A R N I N G rotation personnel with heating equipment experience. Heater should only be serviced by qualified Motor - Disconnect heater from power supply before personnel with heating equipment experience.
  • Page 9: Heat Exchanger Removal Of Single- Motor Unit Heater

    HEAT EXCHANGER REMOVAL OF SINGLE- MOTOR UNIT HEATER HEAT EXCHANGER REMOVAL OF SINGLE- MOTOR UNIT HEATER Remove unit heater from its mounted location and lower to a stable working surface. Remove unit heater from its mounted location and Remove all louver blades from the front of the cabinet. lower to a stable working surface.
  • Page 10: Parts List

    PARTS LIST AH - 12A, - 16A, - 20A, and - 24A FIGURE 17 ITEM AH-12A AH-16A AH - 20A AH-24A AH-24B DESCRIPTION 5378 5382 5386 5390 5394 Panel,AH Top/Bottom 5376 5380 5384 5388 5392 Panel, AH Right Side 5379...
  • Page 11 B12334-01 Terminal Box B12676-07 Trolley, Disco 11362 Bracket, Din 12112 Switch, Disco XS40 Disconnect B12676-07 Terminal Blo XHP100 Dry Seal Plug 11650 Mounting Bra Contact Manufactuer Cable, Teck- Contact Manufacturer Fitting, Teck REV. REVISION D TITLE: KIT, XS40 DISC SWTCH ASSM XS40 DWG NO.: SHEET:...
  • Page 12: General Specifications

    565 lbs. * See page 7 for model coding. ** At 70˚F and sea level. *** Ruffneck reserves the right to substitute motors of higher horsepower. Δ Add 12 lbs to flanged units. Pressure restrictions are for CSA Certified heaters only.
  • Page 13 NOTES...
  • Page 14: Limited 1-Year Warranty

    LIMITED 1-YEAR WARRANTY CCI Thermal Technologies Inc. warrants all Ruffneck™ Advanced Horizontal Series Unit Heaters against defects in materials and workmanship for a period of one (1) year from date of purchase on the following terms: 1. We will provide replacement parts free of charge as necessary to restore any unit to normal operating condition, provided that the inoperative parts be returned to us freight prepaid and that the replacement parts be accepted freight collect.
  • Page 15 LIRE TOUS LES AVIS IMPORTANTS À LA PAGE 3. RESPECTER LES DIRECTIVES DU PRÉSENT GUIDE pour éviter tout danger ainsi que l’annulation de certaines dispositions de la garantie. Ruffneck est une marque déposée. Copyright © 2015. Tous droits réservés. Date d’émission : Avril 2015 N°...
  • Page 16 Photocopier LISTE DE CONTRÔLE DE MAINTENANCE DE L’AÉROTHERME cette page pour la réutiliser. Pour aérothermes à échangeur de chaleur Modèle d’aérotherme : N° de série : Date de maintenance : Maintenance faite par : Commentaires : AVERTISSEMENT Seul un personnel qualifié et expérimenté avec les appareils de chauffage peut effectuer la maintenance de cet aérotherme.
  • Page 17: Avis Importants

    AVIS IMPORTANTS AVERTISSEMENT : AVIS IMPORTANTS Lire et respecter les directives suivantes afin d’éviter tout risque de blessure grave ou mortelle. Veiller à lire et suivre les instructions du présent manuel. Pour une utilisation avec de la vapeur, utiliser exclusivement les modèles à un passage.
  • Page 18 La hauteur maximale à laquelle l’air chaud peut atteindre le Spécifications »); plancher dépend du lieu et des conditions de fonctionnement. Les lames déflectrices peuvent être ajustées pour projeter l’air AH-12A AH-16A AH-20A AH-24A davantage vers le plancher. L’angle de fermeture des lames 15-13/16 19-13/16 23-13/16 27-7/8 déflectrices ne doit pas dépasser 75°...
  • Page 19 INSTALLATION DE TUYAUTERIE Pour utilisation sur système de vapeur, n’utiliser que des INSTALLATION DE TUYAUTERIE aérothermes à une seule passe. Se référer à la section « Codage de modèle » pour connaître le nombre de passestube. Pour utilisation sur système de vapeur, n'utiliser que des aérothermes à...
  • Page 20 AVERTISSEMENT SCHÉMAS DE CÂBLAGE DU MOTEUR L’installation de l'aérotherme doit être effectuée par un personnel qualifié et doit être conforme à tous les codes électriques locaux. Pour le filage et câblage interne des appareils de régulation et SCHÉMAS DE CÂBLAGE DU MOTEUR démarreurs, consulter les fabricants de ces appareils.
  • Page 21: Spécifications

    Acier au carbone à revêtement  phénolique Heresite® REMARQUE: RACCORDS Ruffneck utiliser Doerr/Emerson/Baldor comme moteur standard. L’utilisation d’une autre marque de moteur prolongerait les délais Vissé mâle 1 1/2 po NPT Sch. 40 d’approvisionnement. Tous les échangeurs de chaleur ont un numéro Bride RF 1 1/2 po, 300 lb/po²...
  • Page 22: Réparation Et Remplacement

    RÉPARATION ET REMPLACEMENT R É P A R A T I O N E T R E M P L A C E M E N T Boulons AVERTISSEMENT faisceau de tubes A V E R T I S S E M E N T Rotation du Seul un personnel qualifié...
  • Page 23 D É M O N T A G E D E L ' É C H A N G E U R - A É R O T H E R M E S À 1 M O T E U R S DÉMONTAGE DE L’ÉCHANGEUR - AÉROTHERMES À...
  • Page 24 PARTS LIST AH - 12A, - 16A, - 20A, et - 24A Pour la liste des pièces sectionneurs voir figure 19 FIGURE 17 ARTICLE AH-12A AH-16A AH - 20A AH-24A AH-24B DESCRIPTION 5378 5382 5386 5390 5394 Panneau AH, supérieur/inférieur...
  • Page 25 B12334-01 Terminal Box B12676-07 Trolley, Disco 11362 Bracket, Din 12112 Switch, Disco Sectionneur XS40 B12676-07 Terminal Blo XHP100 Dry Seal Plug 11650 Mounting Bra Contact Manufactuer Cable, Teck- Contact Manufacturer Fitting, Teck REV. REVISION D TITLE: KIT, XS40 DISC SWTCH ASSM XS40 DWG NO.: SHEET:...
  • Page 26: Spécifications Générales

    * Voir page 7 pour le codage de modèle. ** À 70 °F et au niveau de la mer. *** Ruffneck se réserve le droit d’installer des moteurs de plus grande puissance (HP). Δ Ajouter 12 lb pour les aérothermes avec raccords à brides.
  • Page 27 REMARQUES...
  • Page 28: Garantie Limitée De 1 An

    GARANTIE LIMITÉE DE 1 AN Les aérothermes à échangeur de chaleur de série AH (Advanced Horizontal) sont garantis contre tout défaut de fabrication et de main-d’oeuvre pour une période d’un (1) an à partir de la date d’achat, selon les modalités suivantes : 1.

This manual is also suitable for:

Ah-16aAh-20aAh-24a

Table of Contents