To access this display from the ICVC default screen:
1. Press
MENU
.
2. Press
SERVICE
.
3. Scroll down to highlight
EQUIPMENT SERVICE
4. Press
.
SELECT
5. Scroll down to highlight
SETUP1
6. Press
SELECT
DESCRIPTION
Comp Motor Temp Override
Cond Press Override
Comp Discharge Alert
Comp Thrust Brg Alert
Comp Thrust Brg Trip
Thrust Brg Reset Factor
Chilled Medium
Chilled Water Deadband
Evap Refrig Trippoint
Refrig Override Delta T
Evap Approach Alert
Cond Approach Alert
Condenser Freeze Point
Flow Delta P Display
Evap Flow Delta P Cutout
Cond Flow Delta P Cutout
Cond Hi Flow Alarm Opt*
Cond Hi Flow Del P Limit
Water Flow Verify Time
Oil Press Verify Time
Recycle Control
Restart Delta T
Shutdown Delta T
Spare Alert/Alarm Enable
Disable=0, Lo=1/3,Hi=2/4
Spare Temp #1 Enable
Spare Temp #1 Limit
Spare Temp #2 Enable
Spare Temp #2 Limit
*When set to DISABLE, alarm functions as an alert.
NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.
Table 3 — ICVC Display Data (cont)
EXAMPLE 20 — SETUP1 DISPLAY SCREEN
.
.
STATUS
150-200
90-165
125-200
10-20
160-185
1.0-3.0
0/1
0.5-2.0
0.0-40.0
2.0-5.0
0.5-30.0
0.5-30.0
-20 - 35
0/1
0.5 - 50.0
0.5 - 50.0
0/1
0.5-50.0
0.5-5
15-300
2.0-10.0
0.5-4.0
0-4
-40-245
0-4
-40-245
UNITS
DEG F
PSI
DEG F
^F
DEG F
WATER/BRINE
^F
DEG F
^F
^F
^F
DEG F
DSABLE/ENABLE
^PSI
^PSI
DSABLE/ENABLE
PSI
MIN
SEC
^F
^F
DEG F
DEG F
40
POINT
DEFAULT
MT_OVER
200
CP_OVER
125
CD_ALERT
200
TB_ALERT
10
TB_TRIP
185
TB_POWER
1.4
MEDIUM
WATER
CWDB
1.0
ERT_TRIP
33
REF_OVER
3
EVAP_AL
5
COND_AL
6
CDFREEZE
34
FLOWDISP
DSABLE
EVAP_CUT
5.0
COND_CUT
5.0
COND_ALM
DSABLE
COND_VAL
50.0
WFLOW_T
5
OILPR_T
40
rcycr_dt
5
rcycs_dt
1
sp1_en
0
sp1_lim
245
sp2_en
0
sp2_lim
245