Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 205

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Diffuser Control
Diffuser Option
Diffuser Full Span mA
Guide Vane 25% Load (2)
Guide Vane 50% Load (2)
Guide Vane 75% Load (2)
SRD 25% Load (1)
SRD 50% Load (1)
SRD 75% Load (1)
Lift @ 25% Load (1)
Lift @ 100% Load (1)
Lift @ 25% Load (2)
SRD IGV Offset Select
Low Lift Profile Select
NOTE: No variables are available for CCN read or write operation.
19XR, XRV PIC II VDO SRD TABLE CONFIGURATION SHEET .
RANGE
0/1
15 to 22
0 to 83
0 to 83
0 to 83
0 to 100
0 to 100
0 to 100
0 to 100
0 to 55.6
0 to 100
0 to 55.6
0 to 100
0 to 55.6
1 to 5
1 to 5
UNITS
0
mA
18.0
%
6.4
%
22.9
%
41.3
%
73.5
%
35.1
%
19.5
^F
52.4
^C
29.1
^F
67.5
^C
37.5
^F
27.2
^C
15.1
3
3
CL-7
DEFAULT
VALUE