Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 203

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Starter Type
(0=Full, 1=Red, 2=SS/VFD, 3=VFD)
Motor Rated Line Voltage
Volt Transformer Ratio: 1
Overvoltage Threshold
Undervoltage Threshold
Over/Under Volt Time
Voltage% Imbalance
Voltage Imbalance Time
Motor Rated Load Amps
Motor Locked Rotor Trip
Locked Rotor Start Delay
Starter LRA Rating
Motor Current CT Ratio: 1
Current% Imbalance
Current Imbalance Time
Grnd Fault CT's?
Ground Fault CT Ratio: 1
Ground Fault Current
Ground Fault Start Delay
Ground Fault Persistence
Single Cycle Dropout
Frequency-60 Hz? (No=50)
Line Frequency Faulting
19XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET
RANGE
0 to 3
200 to 13200
1 to 115
105 to 115
85 to 95
1 to 10
1 to 10
1 to 10
10 to 5000
100 to 60000
1 to 10
100 to 60000
10 to 1000
5 to 40
1 to 10
0/1
150
1 to 25
1 to 20
1 to 10
0/1
0/1
0/1
UNITS
VOLTS
%
%
SEC
%
SEC
AMPS
AMPS
cycles
AMPS
%
SEC
NO/YES
AMPS
cycles
cycles
DSABLE/ENABLE
NO/YES
DSABLE/ENABLE
CL-5
DEFAULT
VALUE
1
460
1
115
85
5
10
5
200
1000
5
2000
100
15
5
YES
150
15
10
5
DSABLE
YES
DSABLE