Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 204

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Auto Restart Option
Guide Vane Closure
Remote Contacts Option
Soft Stop Amps Threshold
Surge / Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Low Load HGBP=2
Minimum Load Point
Surge/HGBP Delta Tsmin
Surge/HGBP IGVmin
Full Load Point
Surge/HGBP Delta Tsmax
Surge/HGBP IGVmax
Surge Line Shape Factor
Surge Line Speed Factor
Surge Line High Offset
Surge/HGBP Deadband
HGBP On Delta T
HGBP Off Delta T
Surge Protection
Surge Delta% Amps
Surge Time Period
Surge Delay Time
Ice Build Control
Ice Build Option
Ice Build Termination
0=Temp, 1=Contact, 2=Both
Ice Build Recycle
Refrigerant Leak Option
Refrigerant Leak Alarm mA
Head Pressure Reference
Delta P at 0% (4mA)
Delta P at 100% (20mA)
Minimum Output
NOTE: No variables are available for CCN read or write operation.
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
RANGE
0/1
DSABLE/ENABLE
4 to 25
%
0/1
DSABLE/ENABLE
40 to 100
%
0, 1, 2
0.0 to 150.0
ˆF
0.0 to 110.0
%
0.0 to 150.0
ˆF
0.0 to 110.0
%
–1.000 to 0.000
0.00 to 3.00
0.1 to 3.0
0.5 to 3
ˆF
0.5 to 10.0
ˆF
0.5 to 10.0
ˆF
5 to 40
%
7 to 10
MIN
0 to 120
SEC
0/1
DSABLE/ENABLE
0 to 2
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
4 to 20
mA
20 to 85
PSI
20 to 85
PSI
0 to 100
%
UNITS
DEFAULT
DSABLE
4
DSABLE
100
0
45
5.0
70
5.0
–0.040
1.85
1.0
1
2.0
4.0
20
8
0
DSABLE
0
DSABLE
DSABLE
20
25
50
0
CL-6
VALUE