times. The PIC II can be placed in the local operating
mode by pressing the CCN softkey. When RUN STATUS
is READY, the chiller will attempt to start up.
PRIMARY STATUS
MESSAGE
SECONDARY
STATUS
MESSAGE
ALARM LIGHT
(ILLUMINATED
WHEN POWER ON)
BLINKS CONTINUOUSLY
ON FOR AN ALARM
BLINKS ONCE TO
CONFIRM A STOP
STOP BUTTON
HOLD FOR ONE
SECOND TO STOP
SOFT KEYS
EACH KEY'S FUNCTION IS
DEFINED BY THE MENU DESCRIPTION
ON MENU LINE ABOVE
Fig. 17 — ICVC Default Screen
19XR_II
ALARM HISTORY
CONTROL TEST
CONTROL ALGORITHM STATUS
EQUIPMENT CONFIGURATION
ISM (STARTER) CONFIGURATION DATA
EQUIPMENT SERVICE
TIME AND DATE
ATTACH TO NETWORK DEVICE
LOG OUT OF DEVICE
ICVC CONFIGURATION
Fig. 18 — ICVC Service Screen
• OFF — The control is in OFF mode when neither the
LOCAL nor CCN softkey cue is highlighted. Pressing
the STOP key or an alarm will place the control in this
mode. The PIC II control must be in this mode for certain
operations, such as performing a Control Test or access-
ing ISM Configuration parameters.
Force priority — The forces from various sources apply in an
order of priority. Any force can override a force with a lower
priority. The lowest priority belongs to the normal operating
control. A higher force cannot be overridden. For example, a
Service Tool force cannot be overridden by anything but a ma-
chine safety or fire alarm. See Table 4.
ALARMS AND ALERTS — An alarm shuts down the com-
pressor. An alert does not shut down the compressor, but it no-
tifies the operator that an unusual condition has occurred. An
alarm (*) or alert (!) is indicated on the STATUS screens on the
far right field of the ICVC display screen.
Alarms are indicated when the control center alarm light (!)
flashes. The primary alarm message is displayed on the default
screen. An additional, secondary message and troubleshooting
information are sent to the ALARM HISTORY table.
COMPRESSOR
DATE
TIME
ON TIME
RUNNING TEMP CONTROL
01-01-95 11:48
LEAVING CHILLED WATER
28.8 HOURS
CHW IN
CHW OUT
EVAP REF
55.1
44.1
40.7
CDW IN
CDW OUT
COND REF
85.0
95.0
98.1
OIL PRESS
OIL TEMP
AMPS %
21.8
132.9
93
CCN
LOCAL
RESET
MENU
MENU
LINE
SERVICE
When an alarm is detected, the ICVC default screen will
freeze (stop updating) at the time of alarm. The freeze enables
the operator to view the chiller conditions at the time of alarm.
The STATUS tables will show the updated information. Once
all alarms have been cleared (by pressing the
key), the default ICVC screen will return to normal operation.
ICVC MENU ITEMS — To perform any of the operations
described below, the PIC II must be powered up and have suc-
cessfully completed its self test. The self test takes place auto-
matically, after power-up.
Press the
MENU
tures:
,
STATUS
.
SERVICE
• The STATUS menu allows viewing and limited calibra-
tion or modification of control points and sensors, relays
and contacts, and the options board.
• The SCHEDULE menu allows viewing and modification
of the local and CCN time schedules and Ice Build time
schedules.
• The SETPOINT menu allows set point adjustments, such
as the entering chilled water and leaving chilled water set
points.
• The SERVICE menu can be used to view or modify
information on the Alarm History, Control Test, Control
Algorithm Status, Equipment Configuration, ISM Starter
Configuration data, Equipment Service, Time and Date,
Attach to Network Device, Log Out of Network Device,
and ICVC Configuration screens.
For more information on the menu structures, refer to Fig.
20.
Press the softkey that corresponds to the menu structure to
be viewed:
STATUS
SERVICE
. To view or change parameters within any of these
menu structures, use the
scroll down to the desired item or table. Use the
key to select that item. The softkey choices that then appear de-
pend on the selected table or menu. The softkey choices and
their functions are described below.
BASIC ICVC OPERATIONS (USING THE SOFT-
KEYS) — To perform any of the operations described below,
the PIC II must be powered up and have successfully com-
pleted its self test.
• Press
to leave the selected decision or field with-
QUIT
out saving any changes.
• Press
to leave the selected decision or field and
ENTER
save changes.
• Press
to scroll the cursor bar down in order to
NEXT
highlight a point or to view more points below the cur-
rent screen.
22
RESET
softkey to view the list of menu struc-
,
SETPOINT
SCHEDULE
,
SCHEDULE
SETPOINT
and
NEXT
PREVIOUS
SELECT
soft-
,
and
, or
softkeys to
soft-