Carrier AquaEdge 19XR series Start-Up, Operation And Maintenance Instructions Manual page 196

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic ii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

POINT DESCRIPTION
Active Demand Limit
Actual Guide Vane Position
Actual Line Current
Actual Line Voltage
Actual VFD Speed
Calc Evap Sat Temp
Chilled Water Deadband
Chilled Water Delta P
Chilled Water Delta T
Chilled Water Pump
Chilled Water Temp
Chiller S/S
Comp Discharge Temp
Comp Motor Winding Temp
Comp Thrust Brg Temp
Condenser Pressure
Condenser Refrig Temp
Condenser Water Delta P
Control Point
Cond Water Flow
Cond Water Pump
Current CHW Setpoint
Demand Level 1
Demand Level 2
Demand Level 3
Element Communications Alarm
Element Comm Status
Emergency Stop
Entering Chilled Water
Entering Condenser Water
Equipment Alarm
Evaporator Pressure
Frequency
Hardware Failure
Leaving Chilled Water - Prime
Variable
Leaving Condenser Water
Local Schedule
Occupied?
Oil Sump Temperature
Overload Trip
Power Factor
Remote Start Contact
Run Status
Service Ontime
LEGEND
CHW
— Chilled Water
R
— Read
VFD
— Variable Frequency Drive
W
— Write
APPENDIX D — BACNET COMMUNICATION OPTION (cont)
Table G — UPC Open Points List for Version 14 19XR Software
CCN
POINT NAME
DEM_LIM
GV_POS
AMPS_A
VOLT_A
VFD_ACT
ERT
CWDB
CHWPD
CHW_DT
CHWP
CHW_TMP
CHIL_S_S
CMPD
MTRW
MTRB
CRP
CRT
CDWPD
LCW_STPT
CDW_FLOW
CDP
CHWSTPT
N/A
N/A
N/A
N/A
N/A
EMSTOP
ECW
ECDW
N/A
ERP
FREQ
HARDWARE
LCW
LCDW
N/A
OCC
OILT
OVERLOAD
POW_FACT
REMCON
STATUS
S_HRS
READ/
UNITS
RANGE
WRITE
R/W
%
40 to 100
R
%
R
A
R
V
R
%
R
°F
R
^F
R
^F
R
^F
R
R
°F
R/W
STOP/START
R
°F
R
°F
R
°F
R
PSI
R
°F
R
PSI
R/W
°F
-10 to 120
R
R
R
°F
R
%
R
%
R
%
R
R
R
R
°F
R
°F
R
R
PSI
R
Hz
R
R
°F
R
°F
R
R
R
°F
R
R
R/W
OPEN/CLOSE
0=Timeout
1=Ready
2=Recyle
3=Startup
4=Running
5=Demand
R
6=Ramping
7=not used
8=Override
9=Tripout
10=Control
R/W
hr
0 to 32767
196
BACNET
BACNET
OBJECT ID
OBJECT NAME
AV:6
dem_lim_1
AV:7
gv_pos_1
AV:8
amps_a_1
AV:9
volt_a_1
AV:11
vfd_act_1
AV:13
ert_1
AV:14
cwdb_1
AV:15
chwpd_1
AV:16
chw_dt_1
BV:4
chwp_1
AV:17
chw_tmp_1
BV:5
chil_s_s_1
AV:18
cmpd_1
AV:19
mtrw_1
AV:20
mtrb_1
AV:21
crp_1
AV:22
crt_1
AV:23
cdwpd_1
AV:24
lcw_stpt_1
BV:6
cdw_flow_1
BV:7
cdp_1
AV:25
chwstpt_1
dmv_lvl_1_perct_
AV:1
1
dmv_lvl_2_perct_
AV:2
1
dmv_lvl_3_perct_
AV:3
1
com-
BV:20
m_lost_alm_1
BV:2999
element_stat_1
BV:8
emstop_1
AV:26
ecw_1
AV:27
ecdw_1
BV:21
element_alarm_1
AV:28
erp_1
AV:30
freq_1
BV:9
hardware_1
AV:31
lcw_1
AV:32
lcdw_1
BV:2
schedule_1
BV:10
occ_1
AV:33
oilt_1
BV:12
overload_1
AV:34
pow_fact_1
BV:11
remcon_1
AV:35
status_1
AV:36
s_hrs_1