Outline Of Control - Daikin VRV K Manual

Table of Contents

Advertisement

SI-95.BOOK Page 15 Friday, March 31, 2000 10:59 AM
Si-95
1.4

Outline of Control

1.4.1
Inverter Compressor, Motorized PI Control
1. Compressor PI control
I Cooling operation
I Heating operation
I Simultaneous cooling/heating operations
∗ TeS setting values
* TcS setting values
2. Motorized valve PI control
Provides PI control for the motorized valves (Y1E and Y2E) to maintain a constant superheat (SH) level at
the outlet of the outdoor heat exchanger (evaporator).
SHs = Ts - Te
SHs = 5˚C
∗ Ts1 :Suction pipe temperature (R4-1T)
Ts2: Suction pipe temperature (R4-2T)
3. Heat exchanger PI control
Provides PI control for the motorized valve (Y1E) to maintain TeS and TcS at constant.
Motorized valve mode
Functions Inverter K Series
Controls TeS (target Te value) at constant ··· Constant-level control of Te (low pressure equivalent
saturation temperature)
TeS = 5.5˚C
Controls TcS (target Tc value) at constant ··· Constant-level control of Tc (high pressure equivalent
saturation temperature)
TcS = 48˚C
Controls TeS and TcS at constant
TeS = 5.5˚C
TcS = 48˚C
L
M
(Factory setting)
2.5
5.5
L
M
(Factory setting)
43
46
EV mode
Initial opening Max. opening
1
Y1E
2000
Y2E
2000
2
Y1E
2000
Y2E
0
3
Y1E
750
Y2E
250
4
Y1E
0
Y2E
700
5
Y1E
700
Y2E
500
H
8.5
H
49
Min. opening
Normal opening
2000
2000
Fixed at 2000
2000
2000
Fixed at 2000
2000
1400
Heat exchanger PI control
0
0
Fixed at 0
1400
100
Heat exchanger PI control
400
100
Motorized valve PI control
0
0
Fixed at 0
1000
100
Motorized valve PI control
2000
100
Motorized valve PI control
2000
100
Motorized valve PI control
Functions
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents