Economizer Hood And Two- - Position Hood - Bryant 581Jx14 series Installation Instructions Manual

Single package rooftop, gas heating / electric cooling with puron (r-410a) refrigerant size 14
Table of Contents

Advertisement

4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per the
steps outlined in Economizer Hood and Two–Position
Hood on page 10.
5. If removed, reattach the panel under the damper.
Fig. 12 - - Two- - Position Damper Hood Package Location
Economizer Hood and Two- - Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. If the panel is still attached to the unit, re-
move the screws along the sides and bottom of the
panel. See Fig. 13.
INDOOR
COIL
ACCESS
PANEL
Fig. 13 - - Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful not
to lift the panel too far as it might fall out. Use the
screws provided to attach the hood sides to the hood
top. Use screws provided to attach the hood sides to
the unit. See Fig. 14.
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
C10006
SIDE
PANEL
RAIN DEFLECTORS
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
C10007
SCREW
LEFT
HOOD
SIDE
Fig. 14 - - Economizer Hood Construction
3. Remove the shipping tape holding the economizer
barometric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 14 and 15. Secure hood divider with 3 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Attach the post that separates the filters with the
screws provided.
6. Open the filter clips which are located underneath the
hood top. Insert the aluminum filters into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filters into place. See Fig. 15.
7. Install the two rain deflectors on the edge of the hood
top as shown in Fig. 13.
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 15 - - Economizer Filter Installation
8. Caulk the ends of the joint between the unit top panel
and the hood top as shown in Fig. 13.
9. Replace the filter access panel.
12
TOP
PANEL
INDOOR COIL
ACCESS PANEL
HOOD DIVIDER
C10008
OUTSIDE
AIR
HOOD
FILTER
FILTER
CLIP
C10009